4. Installation, connection and commissioning
Only skilled persons are permitted to carry out the work necessary to in-
stall, commission and run a device or system.
4.1 Mounting
Screw mounting:
Fix the device with four M4 screws; see the dimension graphic on page 22.
4.2 Connecting the device
Wires 1 and 2 (corresponding to "A1" und "A2") have to be connected to the supply vol-
tage
U
s
according to IEC 60364-4-43, which means, the connections have to be protec-
ted against short circuit by means of a protective device (a 6 A fuse is recommended).
Concerning the connection of terminals "L1/+" (red) and "L2/-" (blue) to the IT system to
be monitored, devices for protection against a short circuit in accordance with
IEC 60364-4-43 can be omitted if the wiring is carried out in such a way as to reduce the
risk of a short circuit to a minimum. Only one ISOMETER® may be controlled via an ex-
ternal Test/Reset button. The parallel connection of several test or reset inputs for com-
bined testing of ISOMETER®s is not allowed.
DANGER
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
An electric shock
Damage to the electrical installation
De
s
truction of the device
Before installing and connecting the device, make sure that the
installation has been de-energised. Observe the rules for working on
electrical installations.