Data access using the Modbus RTU protocol
Data access using the Modbus RTU protocol
isoBAT425_D00308_04_M_XXEN/07.2020
24
7.3 Exception code
If a request cannot be answered for whatever reason, the ISOMETER® will send a so-called
exception code with which possible faults can be narrowed down.
7.3.1 Structure of the exception code
Exception code
Description
0x01 Impermissible
function
0x02 Impermissible
data
access
0x03 Impermissible
data
value
0x04 Internal
fault
0x05
Acknowledgement of receipt (answer will be time-delayed)
0x06
Request not accepted (repeat request, if necessary)
Byte Name
Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code (0x03) + 0x80
0x83
Byte 2
Data (exception code)
0x04
Byte 3, 4
CRC16 Checksum
0xE133