Operation of the device
Operation of the device
isoBAT425_D00308_04_M_XXEN/07.2020
21
5.5 "t" menu
5.5.1 Time configuration
FAC
= Factory setting;
Cs
= Customer settings
5.6 "SEt" menu
5.6.1 Function configuration
FAC
= Factory setting;
Cs
= Customer settings
Display
Setting value
Description
Value range FAC
Cs
t
0 … 10
0
s
Start-up delay during device start
ton
0 … 99
0
s
Response delay K1 and K2
toff
0 … 99
0
s
Delay on release K1 and K2
test
OFF / 1 / 24
OFF
h
Repetition time, automatic device test
Display
Activation
Setting value
Description
FAC
Cs
Value
range
FAC
Cs
off
0 . . . 999
0
Password for parameter setting
t
Auto 0.8
Auto 2.0
0.8
2.0
4.0
8.0
2.0
s
Measuring pulse period duration
Period durations with identifier
"auto" change to
the period duration 8.0 s with the
message "Battery voltage
U
n
is ok".
nEt
on
Test of the system connection
during device test E.02
S.Ct
on
Device test during device start
FAC
Restore factory settings
SYS
For Bender Service only
5.7 Measured value display and history memory
R
F
is continuously indicated on the display (standard display). All other measuring value
displays switch to the standard display after a maximum of 5 minutes. The pulse symbol
indicates a current measured value. If this symbol does not appear, the measurement is
still running and the latest valid measured value will be displayed. The symbols
<
or
>
will
be displayed additionally to the measured value when a response value has been
reached or violated, or the measured value is below or exceeds the measuring range.
:
The measured value is indicated in the history memory.
HiS
Display
Description
±R kΩ
Insulation resistance
R
F
1 kΩ ... 10 MΩ Resolution 1 kΩ
For
R
F
< 5 MΩ, "+" or "-"
R
F
indicate as mainly on L+ or L- when |fault
location| > 20 % or strings are open and
|
U
L+e
+
U
L-e
|
≥
5 V.
C
μF
System leakage capacitance
C
e
1
nF
... 9.99
μF
Resolution 1
nF
No update when
R
F
is < 10 kΩ.
U L1 L2 = V
Nominal system voltage L+ - L-
U
n
0 V
DC
… ±99.9 V
DC
Resolution 0.1 V
DC
±100 V
DC
… ±500 V
DC
Resolution 1 V
DC
U L1
=
V
Residual voltage L+ - PE
U
L+e
0 V
DC
… ±99.9 V
DC
Resolution 0.1 V
DC
±100 V
DC
… ±500 V
DC
Resolution 1 V
DC
U L2
=
V
Residual voltage L-
- PE
U
L-e
0 V
DC
… ±99.9 V
DC
Resolution 0.1 V
DC
±100 V
DC
… ±500 V
DC
Resolution 1 V
DC
±R %
Fault location in %
-100 % …+100 %
This value is indicated in the range of the correct total battery voltage
and is only valid for external errors which are directly applied to the
plus or minus connections of the complete battery.
R
e+
= (200 % *
R
e
) / (100 % + x %)
R
e-
= (200 % *
R
e
) / (100 % - x %)