Operation of the device
Operation of the device
isoBAT425_D00308_04_M_XXEN/07.2020
20
5.4 "out" menu
5.4.1 Configuration of the alarm relay operating mode
FAC
= Factory setting;
Cs
= Customer settings
5.4.2 Alarm relay alarm assignment "r1" and "r2" and LED assignment
In the alarm assignment, each alarm is assigned to the corresponding alarm relay with the
setting "on". The LED indication is directly assigned to the alarms and is not related to the
alarm relays.
In the event of an asymmetrical insulation fault, only the alarm corresponding to the as-
signed conductor (L+ or L-) will be displayed. .
Alarm relay K1
Alarm relay K2
Description
Display
FAC
Cs
Display
FAC
Cs
n.c.
n.c.
Operating mode of the alarm relay
n.c./n.o.
K1 "r1"
K2 "r2"
LEDs
Alarm
description
Display
FAC Cs
Display
FAC
Cs
ON
AL1
AL2
off
on
Device error E.xx
r1
+R1 < Ω
off
r2
+R1 < Ω
on
Pre-alarm R1
Fault
R
F
at L+
r1
-R1 < Ω
off
r2
-R1 < Ω
on
Pre-alarm R1
Fault
R
F
at
L-
r1
+R2 < Ω
off
r2
+R2 < Ω
on
Alarm R2
Fault
R
F
at
L+
r1
-R2 < Ω
off
r2
-R2 < Ω
on
Alarm R2
Fault
R
F
at L-
r1
U < V
off
r2
U < V
off
Alarm
U
n
undervoltage
r1
U > V
off
r2
U > V
on
Alarm
U
n
Overvoltage
r1
U
V
on
r2
U
V
off
Message
battery voltage
U
n
is ok
r1
test
off
r2
test
off
Manually
started
device test
1
2
1
Err
2
Err
FAC
= Factory setting;
Cs
= Customer settings
:
LED off
:
LED flashes
:
LED on
5.4.3 Fault memory configuration
FAC
= Factory setting;
Cs
= Customer settings
5.4.4 Interface configuration
FAC
= Factory setting;
Cs
= Customer settings;
( ) = User setting that is not modified by FAC.
r1
S.AL
off
r2
S.AL
off
Device start with
alarm
Display
FAC
Cs
Description
M
off
Memory function for alarm messages (fault memory)
Display
Setting value
Description
Value range
FAC
Cs
Adr
0 / 3 … 90
3
( ) BusAdr.
Adr = 0 deactivates BMS and activates
the isoData data logger with conti-
nuous data output (115k2, 8E1)
Adr 1
--- /
1.2k … 115k
“
---
“ ( ) Baud rate
“---“ --> BMS bus (9k6, 7E1)
"1.2k" … "115k" --> Modbus (variable,
variable)
Adr 2
8E1
8o1
8n1
8n2
8E1
( )
Modbus
8E1
- 8 data bits
even parity, 1 stop bit
8o1
- 8 data bits
odd parity, 1 stop bit
8n1
- 8 data bits
no parity, 1 stop bit
8n2
- 8 data bits
no parity, 2 stop bit
K1 "r1"
K2 "r2"
LEDs
Alarm
description
Display
FAC Cs
Display
FAC
Cs
ON
AL1
AL2