Operation of the device
Operation of the device
isoBAT425_D00308_04_M_XXEN/07.2020
19
5.2 Menu overview
Menu item
Parameter
AL
Querying and set response values
out
Configuring fault memory, alarm relays and interface
t
Setting delay times and self test cycles
SEt
Setting device control parameters
InF
Querying software version
HiS
Querying and clearing the history memory
ESC
Going to the next higher menu level
Enter
or
t > 5 min.
k
R
Standard display
R [kΩ]
C [μF]
U L1 L2 [V
]
UL1 [V
]
UL2 [V
]
R [%]
Measurement display
Menu
Esc
Menu selection
AL
out
t
SEt
InF
HiS
ESC
Enter
Esc
P
1
. . .
P
n
ESC
Optional Password
Edit parameters
Save parameters
Enter
Enter
Enter
Esc
Function
Button
Application
Enter
Menu
Esc
Test
Reset
Select, acknowledge input
Call menu
Exit menu item
Start device test
Clear fault memory
/ MENU
Kurz
> 1,5 s
> 1,5 s
> 1,5 s
> 1,5 s
/ MENU
/ MENU
/ T
/ R
Parameter selection
5.3 "AL" menu
5.3.1 Response value setting
The two parameters that monitor the insulation resistance
R
F
, "R1" and "R2", can be found
in the response value menu "AL". The value R1 can only be set higher than the value R2.
If the insulation resistance
R
F
reaches or falls below the activated values R1 or R2, this
leads to an alarm message. If
R
F
exceeds the values R1 or R2 plus the hysteresis (see table
below), the alarm will be cleared.
The parameters ("U <" and "U >") for monitoring the mains voltage can also be activated
or deactivated in the "AL" response value menu. The maximum undervoltage value is
limited by the overvoltage value.
FAC
= Factory setting;
Cs
= Customer settings
Display
Activation
Setting value
Description
FAC
Cs
Value range
FAC
Cs
R1 <
R2 … 5000
1500
kΩ
Pre-alarm value
R
an1
Hys. = 25 %/min. 1kΩ
R2 <
10… R1
1000
kΩ
Alarm value
R
an2
Hys. = 25 %/min. 1kΩ
U1 <
U1> … 500
400
V
Battery volt. ok
U
BattH
Hys. = 5 %/min. 2 V
U1 >
3 … U1<
378
V
Battery volt. ok
U
BattL
Hys. = 5 %/min. 2 V
U2 <
U2> … 500
345
V
CrossFault
U
CrossH
Hys. = 5 %/min. 2 V
U2 >
3 … U2<
6
V
CrossFault
U
CrossL
Hys. = 5 %/min. 2 V