Settings
Settings
iso685-x-B_D00177_07_M_XXEN/07.2019
38
9.2
(5.3.2.4) Std. GW(manual configuration)
If a standard gateway is used in your network, enter its IP address here. If there is no ga-
teway in the network, enter an address not yet used in the address range as gateway add-
ress.
The device cannot be acccessed without setting a standard gateway address.
Contact your network administrator for information on the configuration of your local
network.
9.2
(5.3.2.5) DNS server
If a DNS server is used, enter the server's IP address. For questions regarding the configu-
ration of a DNS server, contact your network administrator.
9.2
(5.3.2.6) Domain
Enter the domain. For questions regarding the configuration of the domain, contact your
network administrator.
9.2
(5.3.3) BCOM
Set the parameters for communication with other devices via BCOM.
9.2
(5.3.3.1) System name
Set the system name of the network in which the devices are located. In order to guaran-
tee that all devices are able to communicate via BCOM, all devices must have the same
system name.
9.2
(5.3.3.2) Subsystem
Configure the subsystem address of the network in which the devices are located. The de-
vices can communicate with subsystems with the same or different subsystem addresses.
9.2
(5.3.3.3) Device address
Assign a device address. Each device must have a different address to distinguish it from
others in the system and ensure correct communication.
9.2
(5.3.3.4) Timeout
Set the timeout for messages between 100 ms…10 s. This time specification defines the
maximum permissible time for a device to respond.
9.2
(5.3.3.5) TTL for subscription
Set a time between 1 s…1092 min.
This time defines the intervals at which the ISOMETER® sends messages to e.g. a gateway.
Severe alarms (e.g. insulation alarms or substantial value changes) are always sent
immediately.
9.2
(5.3.4) Modbus/TCP
Settings for communication with other devices via Modbus TCP.
9.2
(5.3.4.1) Port 502
Choose whether Modbus TCP should be used:
9.2
(5.3.5) RS-485
Set the parameters for communication with other devices via the Bender sensor bus.
9.2
(5.3.5.1) BS bus
9.2
(5.3.5.2) isoData
9.2
(5.3.6) Modbus RTU
9.2
(5.4) Display
Adjust the display brightness for the ISOMETER® in the "Display" menu:
9.2
(5.4.1) Brightness
Adjust the display brightness between 0 % and 100 % in steps of 10.
If no button is pressed on the display for 15 minutes, the brightness of the display is re-
duced. If now a button is pressed, the normal brightness is restored.
•on
Modbus TCP can be used for communication with other devices.
•off
Modbus TCP cannot be used for communication with other devices.
1. Mode:
Selecting an RS-485 protocol
2. BS bus
BS bus settings
3. isoData
isoData settings
4. Modbus RTU
Modbus RTU settings (Remote Terminal Unit)
1. Address
Address adjustable from 1…90
1. Protocol
Mode adjustable 1, 2 or 3
1. Address
Entering an address from 1…247
2. Baud rate
Setting 9.6 | 19.2 | 37.4 | 57.6 | 115 kbaud
3. Parity
Setting "even" | "odd" | "none"
4. Stop bits
Setting "1" | "2" | "off"