3. Function
3.1 Features
•
Insulation monitoring of AC and 3(N)AC systems with low leakage capacitance (< 200 nF)
•
Fast tripping due to the patented SSCP (Synchronous Sine Correlation Principle) measuring method:
Notification of an insulation fault or shutdown within 150 ms
•
Measuring the impedance between the system and earth (detection of ohmic and capacitive insulation
faults)
•
Response value Zan: 10 kΩ…1000 kΩ
•
Configurable interference detection for the active method (Interference level, consecutive number of
disturbed measurement periods) with the possibility of triggering a device fault in the event of conti-
nuous interference
•
Measuring the neutral point shift to earth (UN-PE)
•
Visual signalling of alarms, or connection or device errors via LEDs
•
2 redundant signaling relays for the notification of insulation faults
•
Connection monitoring of L1/+, L2/–
•
Monitoring of the earth connections E/KE
•
Self test at device start with automatic notification in the event of a fault
•
iso1685FR: RS-485 interface (BMS bus) to output measured values and for configuration
•
iso1685FRM: RS-485 interface (BMS bus and Modbus RTU; switched using the DIP switch)
The BMS bus is used to output measured values and to configure the device.
Modbus RTU is used to communicate with the Modbus-analogue converter M-7024. By means of the
converter, the iso1685FRM provides an analogue output.
•
μSD card with data logger and history memory for alarms
•
Protection against unauthorized or accidental parameter changes
3.2 Product description
3.2.1 General product description
The ISOMETER® iso1685FR… is an insulation monitoring device for IT systems in accordance with IEC 61557-8.
It is applicable for use in AC systems.
3.2.2 Particularities of the ISOMETER® iso1685FRM
The only difference between the ISOMETER® iso1685FRM and the ISOMETER® iso1685FR is the following:
By means of the Modbus-analogue converter M-7024, the ISOMETER® iso1685FRM provides an analogue out-
put. Communication takes place via Modbus RTU. The DIP switch can be used to switch between the BMS and
Modbus protocol.
Further information is available in the following chapter:
•
Activating the Modbus RTU protocol:
"chapter ISOMETER®s iso1685FRM DIP switch assignment"
•
Connection:
"chapter 5.2.3 Anschlussplan mit Modbus RTU (ISOMETER® iso1685FRM)"
und
"chapter 5.2.5 Step-by-step connection of the iso1685FRM ISOMETER®"
Summary of Contents for ISOMETER iso1685FR
Page 6: ...6 ...
Page 10: ...Important information 10 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 14: ...Safety instructions 14 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 42: ...Diagram for the calculation of Ze 42 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 44: ...Information about the measuring method 44 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 50: ...INDEX 50 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 51: ...INDEX 51 iso1685FR M _D00002_02_M_XXEN 06 2017 ...