Commissioning
33
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
6.3.5
Setting response value
R
an2
for alarm 2
Set the response value for the main alarm here.
A value of 50 Ω/V is recommended for the main alarm.
6.3.6
Setting the EDS mode (isoxx1685DP only)
Set the mode for the insulation fault location to manual, automatic or 1 cycle. For further in-
formation, refer to
.
6.3.7
Setting the EDS current (isoxx1685DP only)
Set the maximum locating current.
EDS441: 1-5 mA
EDS440: 10-50 mA
For further information, refer to
Alarm 2
x.x.x
10 kΩ
Min.
1 kΩ
Max.
10 MΩ
Commissioning
x.x
Please set
the response value
R(an2) for
Alarm 2.
x/xx
Mode
x.x.x
o Manual
• Auto
o 1 cycle
Commissioning
x.x
Please set the
desired EDS operating
mode.
Current
x.x.x
o 1mA
• 2.5mA
o 5mA
o10mA
o25mA
Commissioning
x.x
Please select
the EDS current now
x/xx