Operation and setting
58
IRDH575_D00089_05_M_XXEN/01.2020
6.6
EDS-SETUP menu: Settings for fault location
This menu allows to carry out the necessary settings for the insulation fault lo-
cation system (EDS).
6.6.1
EDS auto / on / off / pos / 1cycle
A selection of the start and stop conditions for EDS systems and their meaning
are listed below:
on
The EDS is running continuously, regardless of the insulation value and
the alarm messages from the ISOMETER®. This setting is essential, for
example, for mobile insulation fault location systems such as EDS3060/
3360.
off
The EDS system is constantly switched off.
pos470 (EDS47… only)
For continuous measurement at a desired address (EDS4…-12) and a
certain channel. The selected parameters are kept until a new operat-
ing mode is set.
This function is only possible in the Master mode (bus address 1).
The following messages are possible in the POSITION mode.
Note: the messages noCT and short are only generated when the CT
monitoring for the respective channel has been switched on (= factory
setting, menu CT SETUP):
– no EDS:
no EDS47… of this address available
– no Alarm:
no insulation fault detected
– … mA:
indication of the fault current in case of an insula-
tion fault
– >1A/>10 A:
AC residual current > 1 A (EDS473) or >10 A
(EDS470)
– peak fault:
measurement disturbed
– short:
CT input short-circuited
– noCT:
no CT connected