Serial interfaces
70
IRDH375_D00124_05_M_XXEN/01.2020
7.2 RS-485 interface with BMS protocol (IRDH375B)
The RS-485 interface galvanically isolated from the device electronics and cur-
rent output serves as a physical transmission medium for the BMS protocol. If
several IRDH375B or other bus-capable devices are interconnected in a net-
work via the BMS bus, the BMS bus must be terminated at both ends with a
120 Ω resistor.
An RS-485 network that is not terminated, is likely to get instable and may re-
sult in malfunctions. Only the first and the last device in one line may be ter-
minated. Devices in between must not be terminated with 120 Ω. Hence, stub
feeders in the network must not be terminated. The length of the stub feeders
is restricted to 1 m.
A
B
A
B
A
B
1st device
... device
last device
120
W
0.4 W
120
W
0.4 W
Stub feeder
maximum 1 m
Maximum length of the RS485 bus: 1200 m