Operation and setting
54
IRDH275_D00122_03_M_XXEN/05.2017
6.5
Menu ISO ADVANCED: Setting of the extended
functions
6.5.1
External coupling devices (AGH: no)
Basic setting "no", when no coupling device is used (factory setting).
AGH: 204 AK80
Terminal AK of the IRDH275 is connected to terminal AK80 of the
AGH204S-4. The nominal voltage range is extended to 3AC 0…1650 V. Only
current converters with an output voltage not exceeding DC 1000 V are al-
lowed to be connected (see "operation with coupling device" on page 34).
AGH: 520S
Terminal AK of the IRDH275 is connected to terminal 5 of the AGH520S. The
nominal voltage range is extended to AC 0…7200 V. Only current converters
with an output voltage not exceeding DC 1000 V are allowed to be connected.
AGH: 204 AK160
Terminal AK of the IRDH275 is connected to terminal AK160 of the
AGH204S-4. The nominal voltage range is extended to 3AC 0…1300 V. Only
current converters with an output voltage not exceeding DC 0…1840 V are al-
lowed to be connected (see page 34).
AGH: 150 AK160
Terminal AK of the IRDH275 is connected to terminal AK160 of the
AGH150W-4. The nominal voltage range is extended to DC 0…1760 V.
The coupling monitoring is deactivated when an external
coupling device is connected.
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...