Operation and setting
53
IRDH275_D00122_03_M_XXEN/05.2017
6.4.3
Memory setting (on/off)
Memory: on
= Fault memory is activated
The device must be reset with the RESET button after
clearing the fault.
Memory: off
= Fault memory deactivated (factory setting)
6.4.4
Current output for external measuring instruments
(IRDH275B)
Factory setting: 0…20 mA
The current output of the IRDH275 can be set to "0…20 mA" or "4…20 mA" via
the menu point "M+/M-:". The maximum load is 500 Ω.
Function 0…20 mA:
R
F
= insulation fault, I= current in mA
Function 4…20 mA:
R
F
= insulation fault, I= current in mA
The associated characteristic curves are illustrated on page 83.
During the automatic self test, the alarm relays are not
switched over.
When a device fault occurs at the ISOMETER®
,
the relay K2
will automatically be activated as a device fault relay.
Ω
Ω
Ω
Ω
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...