4. Connection
4.1
Wiring
Connect the terminals A1/+ and A2/- to the supply voltage
U
S
in accordance
with IEC 60364-4-43. The connections to the supply voltage shall be provided
with protective devices to afford protection in the event of a short circuit
(a 6 A fuse is recommended).
For UL and CSA applications, the use of 5 A fuses is mandatory.
Devices for protection against short-circuit in conformity with IEC 60364-4-43
for the IT system coupling L1/L2 can be omitted if the wiring is carried out in
such a manner as to reduce the risk of a short-circuit to a minimum (a short-
circuit-proof and earth-fault-proof wiring is recommended).
Only
qualified personnel
are permitted to carry out the
work necessary to install, commission and run a device or
system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
•
An electric shock
•
Damage to the electrical installation
•
Destruction of the device
Before installing and connecting the device
,
make sure
that the
installation
has been
de-energised
. Observe the
rules for working on electrical installations.
DANGER
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...