Application of the internal OPC server
66
8.3.4
Monitoring of the compiled BMS addresses, BMS channels and items
1. Select "DA Items" using the respective tab.
2. The numerical values referring to the items already selected will be displayed in the column "Value".
Interpretation:
Value-Item = 30 ==> Numerical value 30 (BMS data value)
Type-Item = 55 ==> Residual current in mA (BMS data type)
Alarm-Item = 1 ==> Alarm message (BMS alarm)
The BMS device with address 5 provides an alarm message on channel 2:
The measured residual current has exceeded or has fallen below a predefined response value.
The second value triple shows the same residual current, but no alarm message. On channel 4, the
measured residual current lies within the tolerances relating to a second response value (discrimina-
tor circuit).
The relationship between Type-Item and BMS data type
A "Type-Item" is the type of fault that initiated an alarm. It corresponds to the BMS data value
and is listed in the table "alarm messages" on page 67.
3.