Programming examples
62
FTC470XDP_D00111_00_M_XXEN/02.2015
7.3 Requesting the measuring values via channel number
The following examples only differ in their replies.
The PROFIBUS Master addresses BMS address 7, the RCMS470-12 residual current monitor, for infor-
mation about the actual measuring value. This value is available at channel 10.
PROFIBUS Master output data:
The RCMS470-12 replies that a fault current of 100 mA is the measuring value to channel 10.
PROFIBUS Master input data:
The PROFIBUS Master addresses BMS address 7, the RCMS470-12 residual current monitor, for infor-
mation about the actual measuring value. This value is available at channel 10.
PROFIBUS Master output data:
The RCMS470-12 signals a fault current of 9 A as the actual measuring value.
PROFIBUS Master input data:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
10
0
7
10
105
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
10
0
7
10
105
55
0
100
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
11
0
7
10
105
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
11
0
7
10
105
56
0
9