Operation
53
6.6.3.3
Settings menu 3: Relay
You make the settings for the common alarm relays K1 and K2 in this
menu (either individually or common to all alarm relays). Selecting a re-
lay
1. Use the "
S
" key to go to the relay channel setting. Press "
↵
".
2. Use the UP/DOWN keys to select a relay (1, 2) or for both relays (1...2).
Press "
↵
" to confirm your selection.
1.Op.mode
Set the relay mode of operation:
N/O-T
N/O operation. Relay switches in the event of an alarm
or a test.
N/C-T
N/C operation. Relay switches in the event of an alarm
or a test.
N/O
N/O operation. Relay only switches in the event of an
alarm.
N/C
N/C operation. Relay only switches in the event of an
alarm.
2.Alarm
ON
Relay switches in the event of an alarm.
OFF
Relay does not switch in the event of an alarm.
Relay: 1
Exit
1.Relay mode:N/O-T
2.Alarm: on
Setting
a single relay:
Relay: 1...2
Exit
1.Relay mode:N/O-T
2.Alarm: on
Setting
both relays: