![Bender EDS460-DG Operating Manual Download Page 50](http://html1.mh-extra.com/html/bender/eds460-dg/eds460-dg_operating-manual_2731790050.webp)
Operation
50
6.4.3.4
Settings menu 4: History
Here the entire history memory can be deleted. Press the "
↵
" key to con-
firm that the memory is to be cleared.
6.4.3.5
Settings menu 5: language
Select the language for menu and alarm texts.
Setting options: English, Deutsch or Fran
ç
ais.
6.4.3.6
Settings menu 6: Interface
Set the BMS bus address of the EDS460-DG.
Setting range: Address 1…90
6.4.3.7
Settings menu 7: Alarm addresses
Setting of the bus addresses (1...150) externally connected to the BMS
bus, the alarm messages of which are to be displayed on this EDS460-
DG. Set the addresses of devices whose messages are to be displayed to
"on". Addresses set to "on" are monitored for presence on the BMS bus;
if a device cannot be found on the bus, a corresponding message will
appear. The EDS460-DG own address is automatically set to "on".
on
Messages of this device will be displayed.
off
Messages of this device will not be displayed.
Exit
1.Address:
on
2.Address:
off
3.Address:
off