Technical specifications
54
EDS309x_D00012_03_M_XXEN/11.2014
Locating current
PGH183:
Locating current max., can be selected..................................................................................................................................................................1/2.5 mA
PGH185/186:
Locating current max., can be selected.................................................................................................................................................................10/25 mA
PGH183/185/186
Test cycle ............................................................................................................................................................................................................................ 2 s
Pause duration ................................................................................................................................................................................................................... 4 s
Locating voltage
PGH186.......................................................................................................................................................................................................................DC 50 V
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ................................................................................................................ IP40
Enclosure material.................................................................................................................................................................................................ABS plastic
Flammability class....................................................................................................................................................................................................UL94V-0
Weight...................................................................................................................................................................................................................... ≤ 700 g
Dimensions ............................................................................................................................................................................................ 160 x 148 x 81 mm
7.3 Technical specifications EDS195P
( )* = Factory settings
Insulation coordination according to IEC 60664-1/IEC 60664-3
Rated voltage .................................................................................................................................................................................................................. 50 V
Rated surge voltage/degree of pollution ................................................................................................................................................................ 0.8 kV/3
Supply voltage
Power supply
U
S
.................................................................................................................... Rechargeable batteries, batteries or USB power supply unit
Rechargeable batteries......................................................................................................................................................................3 x NiMH ≥ 2000 mAh
Operating time (without display lighting).............................................................................................................................................................. ≥ 150 h
Charging time .............................................................................................................................................................................................................. ≤ 5 h
Size................................................................................................................................................................................................................................ AA R6
Batteries....................................................................................................................................................................................................3 x LR6 AA – 1.5 V
USB power supply unit:
Primary ....................................................................................................................................................................................... 100…240 V, 50…60 Hz
Secondary .................................................................................................................................................................................................... DC 5 V, ± 10 %
Power consumption................................................................................................................................................................................................. ≤ 0.5 W
Measuring circuit, insulation fault location
Nominal system voltage .............................................................................................. With uninsulated conductors with measuring clamp up to 600 V
Rated frequency ....................................................................................................................................................................................... DC, 42…2000 Hz
Main circuit (
I
Lmax
= 50 mA):
Measuring range ................................................................................................................................................................................................. 2…50 mA
Measuring clamps................................................................................................................................................................. PSA3020, PSA3052, PSA3165
Response sensitivity
I
Δ
L
adjustable .................................................................................................................................................... 2… 10 mA (5 mA)*
Operating uncertainty ............................................................................................................................................ ±30 % / ±2 mA of the nominal value
Control circuit: (
I
L
max
= 5 mA)
Measuring range ................................................................................................................................................................................................ 0.2…5 mA
Measuring clamps.................................................................................................................................................................................. PSA3320, PSA3352
Response sensitivity
I
Δ
L
adjustable ............................................................................................................................................. 0.2…1.0 mA (0.5 mA)*
Operating uncertainty 0.2…0.9 mA................................................................................................................. ±30 % / ± 0.2 mA of the nominal value
Operating uncertainty 1…5 mA .......................................................................................................................... ±30 % / ± 2 mA of the nominal value