Parameter overview
25
isoGEN523_D00320_04_M_XXEN/06.2018
5.3 Interface configuration
FAC
= Factory settings;
Cs
= Customer settings;
( ) = User setting that is not modified by FAC
.
5.4 Time configuration
FAC
= Factory settings;
Cs
= Customer settings
Setting value
Description
Available
via
Value range FAC
Cs
BMS Modbus
0 / 3 … 90
3
( ) BusAdr.
Adr = 0 deactivates BMS as well as Mod-
bus and activates isoData with continu-
ous data output
(115k2, 8E1)
X
X
--- /
1.2k … 115k
“
---
“ ( )
Baud
rate
“---“ --> BMS bus (9k6, 7E1)
“1.2k“ … “115k2“ --> Modbus (variable,
variable)
X
X
8E1
8o1
8n1
8E1
( )
M
o
d
b
u
s
8E1
- 8 data bits
even parity, 1 stop bit
8o1
- 8 data bits
odd parity, 1 stop bit
8n1
- 8 data bits
no parity, 1 stop bit
X
Para-
meter
Setting value
Description
Available via
Value
range
FAC
Cs
BMS
Modbus
t
0 … 10
0
s
Start-up delay when starting the
device
X
X
ton
0 … 99
0
s
Response delay K1 and K2
X
X
toff
0 … 99
0
s
Delay on release K1 and K2
X
X
test
OFF / 1 / 24
24
h
Repetition time device test
X
X