Power Quality
40
PEM735_D00084_00_M_XXEN/02.2015
The display shows:
7.3.1
Power Frequency
The power frequency is 50 Hz.
For systems with a synchronous connection to an interconnected system, the DIN EN
50160 requires a nominal frequency
f
n
interval of 49.5…50.5 Hz during 99.5 % of a year
(narrow limits).
All measured values of a year must be in the interval of 47…52 Hz (
f
n
-6 /+ 4 %).
Display text
Description
Note
Timestamp
Observation period for the report
Measured values comply with the
specified threshold values
Measured values do not comply
with the specified threshold values
Detail
Results are shown on several sub-
pages;
Scroll with arrow buttons;
Press "ENTER" or "ESC" to
return to the start page.
When several reports are stored, navigate through the reports using the
and
buttons.
To navigate through individual parameters in the report use the
and
buttons. Press "ENTER" to go to the respective subpage.
Press the "ESC" or "ENTER" button to leave the subpage.
X
Summary of Contents for B 9310 0735
Page 6: ......
Page 10: ...Making effective use of this document 10 PEM735_D00084_00_M_XXEN 02 2015...
Page 18: ...Device description 18 PEM735_D00084_00_M_XXEN 02 2015...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015...
Page 34: ...Operation 34 PEM735_D00084_00_M_XXEN 02 2015...
Page 68: ...Power Quality 68 PEM735_D00084_00_M_XXEN 02 2015...
Page 70: ...Voltage 70 PEM735_D00084_00_M_XXEN 02 2015...
Page 72: ...Current 72 PEM735_D00084_00_M_XXEN 02 2015...
Page 76: ...Waveform 76 PEM735_D00084_00_M_XXEN 02 2015...
Page 80: ...Harmonics 80 PEM735_D00084_00_M_XXEN 02 2015...
Page 84: ...Metering 84 PEM735_D00084_00_M_XXEN 02 2015...
Page 88: ...System 88 PEM735_D00084_00_M_XXEN 02 2015...
Page 102: ...Settings 102 PEM735_D00084_00_M_XXEN 02 2015...
Page 106: ...Technical data 106 PEM735_D00084_00_M_XXEN 02 2015...
Page 112: ...Glossary and terms 112 PEM735_D00084_00_M_XXEN 02 2015...
Page 115: ......