8. Periodic verification and Service
8.1. Periodic verification
The following periodic verification must be performed on electrical installations in compliance with the local
or national regulations that apply. We recommend for your Bender products:
Test
To be
performed by
Interval
Functional test of IT system monitoring
(insulation, load current, transformer temperature and connection
monitoring) by pressing the TEST button on the remote alarm indicator
or on the alarm and control panel.
Medical
personnel
once every
working day
Functional test of the changeover module
*)
Test of the automatic changeover modules. Please observe the
information in chapter "Testing the changeover module"!
Skilled person
every 6 months
Functional test of the IT system monitoring
*)
(insulation, load current, transformer temperature and connection
monitoring) on the insulation monitoring device.
Skilled person
every 6 months
Testing the set values and the changeover periods
*)
Skilled person
every 12
months
Testing of the changeover module
*)
, the IT system monitoring
*)
, the
connection to the SCADA system
*)
(Supervisory Control And Data
Acquisition) if applicable and the interaction of the components in the
system.
This test includes the following services:
- Inspection: Marking, display elements, mechanical components,
wiring, parameterisation, connection of third-party equipment,
evaluation of fault memory
- Measurement: Internal/external supply voltages/potentials, bus
voltage, bus protocol, bus scan
- Practice test: Device function, device communication
- Documentation: Test results, recommendations for remedial action
Bender-Service every 24
months
*)
This test must only be performed by an electrically skilled person who has been commissioned
to do so in agreement with the person responsible for the medical location
Before carrying out the tests, please refer to the instructions relating to the functional tests in the attached
checklist.
If no national directives apply, you should perform the tests recommended by IEC 60364-7-710:2002-11,
section 710.62 and DIN VDE 0100-710 (VDE 0100 Part 710):2002-11, section 710.62.