![Bender ATICS UMA710-2-63-ISO Manual Download Page 33](http://html1.mh-extra.com/html/bender/atics-uma710-2-63-iso/atics-uma710-2-63-iso_manual_2731501033.webp)
Alle Rechte und Änderungen vorbehalten.
Subject to change without notice. All rights reserved.
© Bender GmbH & Co KG
UMA710-2-xx-ISO-xx, Manual.docx
Issued: 11.Jan.2016
33
7.1.2. Messages with Error code or Service code
Error Code/
Service code
Description
Action
1.xx, 9.xx
Fault message from the internal memory
monitoring
- Contact Bender-Service
3.11
Max. number of hours exceeded
- Plan device replacement Alarm
can be cancelled "Reset menu 3:
Changeover" see the technical
manual TGH1443.
3.12
Max. number of changeovers exceeded
- Plan device replacement Alarm
can be cancelled "Reset menu 3:
Changeover" see the technical
manual TGH1443.
3.13
Changeover due to overcurrent or short
circuit.
These changeovers reduce the life
of the device. Currents which are
measured
in excess of 150 times the rated current
are evaluated as over currents or
short-circuit currents
- Have personnel assess the
short-circuit load. Contact Bender
Service. Alarm can be cancelled
see the technical manual
TGH1443
3.5
Service has been carried out. This is not
a fault message. Display only on service
logger
- No action required
6.xx, 7.xx, 8.xx
Device error. The internal self-monitoring
of the device has detected a fault which
could impair the safe operation of the
device.
- Replace device immediately
8.51 … 8.66
Fault during changeover process. Occurs
when the voltage on the new line fails
during the changeover. Also occurs when
the test set-ups do not supply sufficient
current for switching the coils of the
ATICS.
- RESET -> execute alarm, - then
test the changeover function.
- If fault persists: replace the
device.
- Only use test set-ups that can
supply the
necessary peak current
In case a failure occurs, proceed as follows:
1. Activate manual mode, if necessary. (refer to the technical manual TGH1443)
2. Make a note of what happened prior to the fault: operator inputs, device error messages,
environmental conditions, etc.
3. Keep the device type, article and device serial number of the ATICS® to hand.
4. Keep the
project number, job number and drawing number,
according to the type label of the
changeover module or the
Bender
switchgear cabinet to hand.
5. Speak to Bender Service, describe the type of fault and quote the three-digit error code
Please read the chapter „Frequently asked questions“ of he technical manual TGH1443 by Bender.