![Bender ATICS-2-63A-ISO Manual Download Page 60](http://html1.mh-extra.com/html/bender/atics-2-63a-iso/atics-2-63a-iso_manual_2731578060.webp)
60
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Operation
Menu
Description
Exit
Exit "Changeover" reset menu; go up one menu level
1. Changeover: xxx
Number of changeovers performed
2. Alarm: 8000
Alarm value for maximum number of changeovers performed*
Delete
Increase alarm value by 500 changeovers
4. Operat. time: xxh
Operating hours counter (h=hours, d=days, mo=months)
5. Alarm: 120mo
Alarm value for maximum number of operating hours (prewarning after 108
months)*
Delete
The limit value for the permissible number of operating hours is increased by 13
months.
The value is automatically increased by 13 months if the alarm has already been
cleared once before and a successful test of the changeover process is carried out.
7: Changeover I>: 0
Number of changeovers performed which were carried out with overcurrent of
short-circuit current
(see chapter „Menu 2: Changeover“ on p. 64)
8. Alarm: 1
Alarm value for maximum permitted number of changeovers performed which
were carried out with overcurrent or short-circuit current*
Delete
Increase alarm value for changeover in case of overcurrent or short-circuit current
by 1 changeover
* for functional safety according to IEC 61508-2:2010
Delete
Set new alarm value. Clear alarm.
Cancel
Return to reset menu
6.2.4.4 Reset menu 4: Service alarm
• Resetting the service prewarning suppresses the service prewarning until the next service ap-
pointment.
• Resetting the service alarm sets the date for the next service appointment to "current date +
service interval".
Delete
Cancel
Delete
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...