![Bender ATICS-2-63A-ISO Manual Download Page 57](http://html1.mh-extra.com/html/bender/atics-2-63a-iso/atics-2-63a-iso_manual_2731578057.webp)
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 57
ATICS-2-63A-ISO
The display shows the test duration.
I
r
isk
that the generator test is accidentally not completed.
If the test menu 5: "Generator" is left after the generator has started, then ATICS® remains in this
switch position and in "TEST" mode. This means that the generator is not switched off.
- Wait until "Quit: RESET" appears on the display.
- Press the "RESET" button.
- Check whether the generator is switched off.
6.2.3.7 Test menu 6: Test communication
Test communication via the BMS bus. In order to do this, a fault message is simulated. This alarm mes-
sage is sent to evaluator devices (e.g. alarm indicator and operator panels, MK800, SMO…).
Check that these devices are responding to the alarm message as requested.
Select a channel:
1. Use the " " arrow button to go to the channel settings. Press the " " button.
2. Use the arrow buttons to select the channel for which the alarm message is to be simulated.
Press the " " button to confirm your selection.
The alarm status will change from
(no alarm) to
(alarm). If the alarm status
is not displayed,
the settings made for ATICS® will not permit simulation of this alarm.
Example of an alarm simulation: "Channel 5: MANUAL MODE“ is selected.
i
The ATICS® stays in this menu until it is exited by pressing the "ESC" button. During this time, all the
alarms on the BMS bus have the word "TEST".
Only the alarm messages listed in the following table can be simulated: "ATICS® messages on the
BMS bus (channel use)".
Test
t (1->2):
110ms
t (Test):
--
Quit
RESET
Manual mode: --
Exit
Channel: 5 MODE
Channel disabled
Exit
Channel: --
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...