Preliminary Steps
1.
Verify all the parts listed before installing
the linkage.
2.
Choose an actuator from one of the series
listed below. There is a torque reduction
when using the ZG-JSL linkage. Verify
application requirements before use.
* ZG-121 adapter must be used with EF.
** GM/GK not for use with 1/2" shafts.
*** K6-1 clamp must be used with LF.
3.
Determine proper location to install the
linkage onto the damper’s jackshaft. Verify
that there are no obstructions and that the
damper blades do not collide with the
linkage. If available, refer to the damper
manufacturer’s dimensional drawings; the
dimensions of the shaft bearings and
damper blades are usually published.
ZG-JSL Kit Includes:
• Jackshaft Linkage
• "L" Shaped Anti-Rotation Bracket
• Adapter Plate for Anti-Rotation Bracket
• Actuator Anti-Rotation Plate
• Hardware Bag (screws, V-bolt, nuts,
clamp insert, insert holder and bearing sleeve)
• Instruction Sheet
Mounting Installation Instructions
ZG-JSL(A)
®
70756-00001.B
Actuator
Torque Reduction
EF Series*
239 in-lbs
AF Series
166 in-lbs
Classic AF Series
123 in-lbs
NF Series
87 in-lbs
LF Series***
33 in-lbs
GM/GK Series**
288 in-lbs
AM Series
166 in-lbs
NM Series
87 in-lbs
Technical Data
Materials:
Housing
Bearings
Shafts
galvanized steel
GF Delrin
steel
Weight
3.25 lbs [1.47 kg]
1