UK24BAC

 

Belimo Gateway MP to BACnet MS/TP 

 

www.belimo.com 

T9-

UK24BAC • en • v1.9 • 06.2018 • Subject to changes 

5 / 20 

 

 

Electrical installation 

 

Wiring diagram 

 

 

 

 

AC/DC 24 V supply 

Connection via safety isolation 
transformer! 

Dimensioning of the supply 

Also take into account the dimensioning 
specifications of the connected 
MP/MPL/MFT(2) actuators!  

~   

AC 24 V

+    -

DC 24 V

BACnet MS/TP

MPL 

MP

5

2

1

D+
D-

MP
24V

GND

1

2

3

4

MP

MP

MP

5

2

1

3

MP

MP

MP

5

2

1

3

MP

MP

MP

5

2

1

3

 

The wiring of BACnet MS/TP (RS485) is to be carried out in accordance with applicable 
directives. The device possesses resistors which can be switched on for bus connection and 
biasing. 

The GND of the RS485 line is galvanically isolated from the MP-Bus GND. Additional galvanic 
separation shall be provided for segments crossing buildings. 

Connection of the MP-Bus 

  The network consists of a 3-pin connection  

(MP communication and 24 V supply).  

  Possibility of connecting a maximum of 8 MP/MPL/MFT(2) actuators per network. 

  Neither a special cable nor terminating resistors are required. 

  The signal conductor lengths (for calculation, see below) are limited: 

– by the sum of the signal conductor data of the connected MP/MPL/MFT(2) actuators,  
– by the type of supply (AC 24 V via the bus or DC 24 V via the bus),  
– by the signal conductor cross-section. 

With AC 24 V supply:  

Maximum signal conductor length 

L = max. cable length [m] 

 

With AC 24 V supply:  

(minimum transformer voltage 21.6V) 

Total dimensioning 

MP/MPL/MFT(2) actuators [VA] 

 

 

 

 

 

Power rating [VA]

 

 

For the calculation of the maximum cable length, the Belimo MP wiring calculator is available on 
the Belimo website for the complete MP-Bus range. 
 

 

UK24BAC 

More actuators 
and sensors  
(total 8) 

Summary of Contents for UK24BAC

Page 1: ...Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical installation 5 Dimensions 7 Operation 8 Protocol Implementation Conformance Statemen...

Page 2: ...Subject to changes www belimo com Complete overview Gateway MP BACnet MS TP Suitable MP MPL MFT 2 Actuators Damper actuators Fire damper actuators VAV actuators Actuators for characterised control va...

Page 3: ...Supported actuators MP MPL MFT 2 BF TopLine Quantity of actuators max 8 pcs Communication with actuators Belimo MP Bus Master Slave 1200 Bd Maximum signal conductor lengths MP Dependent on the number...

Page 4: ...logue signal of the sensors with the Belimo actuator and transferring it via UK24BAC to the BACnet MPL actuators don t provide a sensor input Installation and commissioning Installation and wiring The...

Page 5: ...aration shall be provided for segments crossing buildings Connection of the MP Bus The network consists of a 3 pin connection MP communication and 24 V supply Possibility of connecting a maximum of 8...

Page 6: ...ite Maximum signal conductor length Wire mm L max cable length m 0 75 800 1 00 1 50 2 50 The signal conductor lengths can be significantly increased if the actuators are supplied with AC 24 V locally...

Page 7: ...the mass of curves For cables with wire mm Cable length m 0 75 55 1 00 75 1 50 110 2 50 190 The power consumption W of the MP MPL MFT 2 actuators used is to be added and the corresponding signal condu...

Page 8: ...tting the BACnet MAC address The BACnet MAC address is set in binary form with the 7 DIP switches under the front cover The valid address range is 1 127 Values outside of this range will be interprete...

Page 9: ...2 and 3 in order to reduce interference effects during communications pauses The biasing is implemented as a rule at one of the bus ends Switches 2 and 3 must always be respectively activated or deac...

Page 10: ...Gateway supports the assigning of addresses to the MP nodes by means of the keys UP OK and DOWN located behind the front cover Procedure 1 Press down the OK key and keep it down approx 2 s until LED1...

Page 11: ...orted Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Data Sharing WritePropertyMultiple B DS WPM B Data Sharing COV Unsolicited B...

Page 12: ...AV n 100 2 Nominal volumetric flow AV n 100 3 Object processing 1 Present_Value writeable for OVERRIDE_ n and COV_MODE 2 Present_Value writable for MIN_STPT_ n und MAX_STPT_ n 3 Only if object comman...

Page 13: ...scard the affected actuator after 10 seconds and reset the actuator type to 0 Monitoring of the actuator is thus accomplished preferably with this object Each MP node has an unambiguous series number...

Page 14: ...for EPIV units 0 65535 SNS_TYPE_ n Multi state Value n 100 3 Sensor type connected to the actuator in the absence of sensor specification the wiring at the Y input of the MP actuator will have the ef...

Page 15: ...tion of the device 20 100 NOM_FLOW_ n Analog Value n 100 3 Nominal volumetric flow or pressure The unit depends on the node type m3 h for VAV controllers Pa for VAV controller in STP mode l min for EP...

Page 16: ...ddressing function reworked Known issues Firmware V1 07 New functions modifications WritePropertyMultiple service supported Feedback values are rounded Unconfirmed COV Notification for Multi state Val...

Page 17: ...UK24BAC Belimo Gateway MP to BACnet MS TP www belimo com T9 UK24BAC en v1 9 06 2018 Subject to changes 17 20...

Page 18: ...UK24BAC Belimo Gateway MP to BACnet MS TP 18 20 T9 UK24BAC en v1 9 06 2018 Subject to changes www belimo com...

Page 19: ...UK24BAC Belimo Gateway MP to BACnet MS TP www belimo com T9 UK24BAC en v1 9 06 2018 Subject to changes 19 20...

Page 20: ......

Reviews: