Belimo NM24P Technical Data Sheet Download Page 1

www.belimo.com

T2-NM24P • en • v1.2 • 03.2010 • Subject to changes

1 / 3

Technical data sheet

NM24P

Technical data

Electrical data

Nominal voltage

AC 24 V, 50/60 Hz / DC 24 V

Nominal voltage range

AC/DC 19.2 ... 28.8 V

Power consumption Operation

At rest

For wire sizing

1.5 W @ nominal torque

0.2 W

4 VA

Connection

Halogen-free cable 1 m, 3 x 0.75 mm

2

Functional data

Torque (nominal torque)

Min. 8 Nm @ nominal voltage

Direction of rotation

Reversible with switch 0 

 resp. 1 

Manual override

Gearing latch disengaged with pushbutton, can be locked

Angle of rotation

Max. 95° , can be limited at both ends with adjustable 

mechanical end stops

Running time

150 s / 90°

Sound power level

Max. 35 dB (A)

Position indication

Mechanical, pluggable

Safety

Protection class

III

 Safety extra-low voltage

Degree of protection

IP66 + IP67

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Rated impulse voltage

0.8 kV (EN 60730-1)

Control pollution degree

4 (EN 60730-1)

Ambient temperature

–30 ... +50°C

Non-operating temperature

–40 ... +80°C

Ambient humidity

100% r.H.

Maintenance

Maintenance-free

Dimensions / Weight

Dimensions

See «Dimensions» on page 3

Weight

Approx. 1.3 kg

Safety notes

!

•  The actuator is not allowed to be used outside the specified field of application, especially in 

aircraft or in any other airborne means of transport.

•  It may only be installed by suitably trained personnel.  

All applicable legal or institutional installation regulations must be complied with.

•  The cover of the protective housing may be opened for adjustment and servicing. When it is 

closed afterwards, the housing must seal tight (see installation instructions).

•  The device on the inside may only be opened up in the factory. It does not contain any parts 

that can be replaced or repaired by the user.

•  The cable must not be removed from the device.
•  When calculating the required torque, the specifications supplied by the damper manufactur­

ers (cross section, design, installation site), and the air flow conditions must be observed.

•  The device contains electrical and electronic components and is not allowed to be disposed 

of as household refuse. All locally valid regulations and requirements must be observed.

Robustline damper actuator for operating 

air dampers in industrial plants and in the 

technical building installations
• For air dampers up to approx. 1.6 m

2

• Torque 8 Nm

 

Nominal voltage AC/DC 24 V

• Control: Open­close or 3­point
Optimum protection against

 

Corrosion and chemical influences

 

UV radiation

 

Damp and condensation

..

..

..

..

..

..

..

..

..

..

..

..

..

.

Reviews: