www.belimo.com
T2-NF24A • en • v1.1 • 06.2011 • Subject to changes
1 / 3
Technical data sheet
NF24A
Technical data
Electrical data
Nominal voltage
AC 24 V, 50/60 Hz / DC 24 V
Nominal voltage range
AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
Power consumption In operation
At rest
For wire sizing
6 W @ nominal torque
2.5 W
8.5 VA
Connection
Cable 1 m, 2 x 0.75 mm
2
Functional data
Torque Motor
Spring return
Min. 10 Nm @ nominal voltage
Min. 10 Nm
Direction of rotation
Can be selected by mounting L / R
Manual override
With hand crank and interlocking switch
Angle of rotation
Max. 95° , can be limited with adjustable
mechanical end stop
Running time Motor
Spring return
≤75 s (0 ... 10 Nm)
≤20 s @ –20 ... 50°C / max. 60 s @ –30°C
Sound power level Motor
Spring return
≤45 dB (A)
≤62 dB (A)
Service life
Min. 60,000 emergency positions
Position indication
Mechanical
Safety
Protection class
III
Extra low voltage
UL Class 2 Supply
Degree of protection
IP54
NEMA2, UL Enclosure Type 2
EMC
CE according to 2004/108/EC
Certification
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Mode of operation
Type 1.AA
Rated impulse voltage
0.8 kV
Control pollution degree
3
Ambient temperature
–30 ... +50°C
Non-operating temperature
–40 ... +80°C
Ambient humidity
95% r.h., non-condensating
Maintenance
Maintenance-free
Dimensions / Weight
Dimensions
See «Dimensions» on page 3
Weight
Approx. 1.8 kg
Spring return actuator with emergency
function for adjusting air dampers in
ventilation and air conditioning systems
in buildings
• For air dampers up to approx. 2 m
2
• Torque 10 Nm
• Nominal voltage AC/DC 24 V
• Control: Open-close