background image

www.belimo.com

T2-NF24A-SR-S2 • en • v1.1 • 04.2011 • Subject to changes

1 / 3

Technical data sheet

NF24A-SR-S2

Modulating spring return actuator with 

emergency function for adjusting air 

dampers in ventilation and air conditioning 

systems in buildings
• For air dampers up to approx. 2 m

2

• Tor�ue ��� Nm

Tor�ue ��� Nm

 ��� Nm

• Nominal voltage AC/DC 24 V

• Control�� modulating DC �� ... ��� V

Control�� modulating DC �� ... ��� V

• Position feedback DC 2 ... ��� V

• Two integrated auxiliary switches

Two integrated auxiliary switches

Technical data

Electrical data

Nominal voltage

AC 24 V, 50/60 Hz / DC 24 V

Nominal voltage range

AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V

Power consumption In operation

At rest

For wire sizing

3.5 W @ nominal torque

2.5 W

5.5 VA

Auxiliary switch

2 x SPDT, 1 mA ... 3 (0.5) A, AC 250 V 

(1 x fix 10% / 1 x adjustable 10 ... 90%)

Connection Motor

Auxiliary switch

Cable 1 m, 4 x 0.75 mm

2

Cable 1 m, 6 x 0.75 mm

2

Functional data

Torque Motor

Spring return

Min. 10 Nm @ nominal voltage

Min. 10 Nm

Control Control signal Y

Operating range

DC 0 … 10 V, input impedance 100 k�

DC 2 … 10 V

Position feedback (measuring voltage U)

DC 2 … 10 V, max. 0.5 mA

Position accuracy

±5%

Direction of rotation Motor

Spring return

Reversible with switch 

 / 

Can be selected by mounting L / R

Manual override

With hand crank and interlocking switch

Angle of rotation

Max. 95° , can be limited with 

adjustable mechanical end stop

Running time Motor

Spring return

≤150 s (0 ... 10 Nm)

≤20 s @ –20 ... 50°C / max. 60 s @ –30°C

Sound power level Motor

Spring return

≤40 dB (A) @ 150 s running time

≤62 dB (A)

Service life

Min. 60,000 emergency positions

Position indication

Mechanical

Safety

Protection class

III

 Extra low voltage

UL Class 2 Supply

Degree of protection

IP54

NEMA2, UL Enclosure Type 2

EMC

Low-voltage directive

CE according to 2004/108/EC

CE according to 2006/95/EC

Certification

Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14

cULus according to UL 60730-1A and UL 60730-2-14

and CAN/CSA E60730-1:02

Mode of operation

Type 1.AA.B

Rated impulse voltage Actuator

Auxiliary switch

0.8 kV

2.5 kV

Control pollution degree

3

Ambient temperature

–30 ... +50°C

Non-operating temperature

–40 ... +80°C

Ambient humidity

95% r.h., non-condensating

Maintenance

Maintenance-free

Dimensions / Weight

Dimensions

See «Dimensions» on page 3

Weight

Approx. 2.0 kg