Technical Data

LMQB24-1

LMQX24-1

Power Supply

24 VAC ±20% 50/60 Hz
24 VDC ±10%

Power Consumption

12 W (1.5 W)

Transformer Sizing

18 VA (Class 2 power source) (Imax 20A@5ms)

Electrical Connection

3 ft plenum rated 
cable

3, 10 or 16 ft 
plenum rated cable

Overload Protection

electronic throughout 0 to 95° rotation

Control

On/Off

Input Impedance

600 

Ω

Angle of Rotation

max. 95°, adjust. with mechanical stop

Torque

35 in-lb [4 Nm]

Direction of Rotation

reversible with             switch

Position Indication

reflective visual indicator (snap-on)

Manual Override

external push button

Running Time

2.5 seconds

2.5, 5 or 10 seconds

constant independent of load

Humidity

5 to 95% RH non-condensing (EN 60730-1)

Ambient Temperature

-22°F to +122°F [-30°C to +50°C]

Storage Temperature

-40°F to +176°F [-40°C to +80°C]

Housing

NEMA 2/IP54

Housing Material

UL94-5VA

Agency Listings

UL 60730-1 A/-2-14, CAN/CSA 
E60730-1:02, CSA C22.2 No. 24-93, CE 
according to 2004/108/EC and 89/336/EEC

Noise Level

<52 dB(A)

Servicing

maintenance free

Quality Standard

ISO 9001

Weight

1.8 lbs [0.85 kg]

Rated Impulse Voltage 800V, Type of action 1, (1.B for -S version), Control Pollution 
Degree 3.

Application

  For On/Off control of dampers in HVAC systems. Actuator sizing should be 
done in accordance with the damper manufacturer’s specifications. 

The actuator is mounted directly to a damper shaft from ½” up to 1.05” in 
diameter by means of its standard universal clamp.

Operation

   The actuator is not provided with and does not require any limit switches, 
but is electronically protected against overload. The anti-rotation strap 
supplied with the actuator will prevent lateral movement.

The LMQB(X) series provides 95° of rotation and a visual indicator 
which indicates position of the actuator. When reaching the damper or 
actuator end position, the actuator automatically stops. The gears can be 
disengaged with manual release on the actuator cover. 

The LMQB(X)24-1 actuators use a sensorless Brushless DC motor, which 
is controlled by an Application Specific Integrated Circuit (ASIC). The 
ASIC monitors and controls the actuator’s rotation and provides a digital 
rotation sensing (DRS) function to prevent damage to the actuator in a 
stall condition. Power consumption is reduced in holding mode.

Add-on auxiliary switches or feedback potentiometers are easily fastened 
directly onto the actuator body for signaling and switching functions.

Dimensions

 (All numbers in brackets are in millimeters.)

LMQB24-1, LMQX24-1

   Quick On/Off Control, Non-Spring Return, 
Direct Coupled, 24V

 Torque min. 35 in-lb for control of damper surfaces up to 11 sq ft.

4 1

LMQX24 1

1.97”

 [50]

4.88” [124]

4.76” [121]

1.61” [41]

0.98” [25]

3.15”

 [80]

2.95”

 [75]

Summary of Contents for LMQB24-1

Page 1: ...in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft from up to 1 05 in diameter by means of its standard universal clamp Operation The actuator is not provided with and does not require any limit switches but is electronically protected against overload The anti rotation strap supplied with the actuator will prevent lateral movement The LM...

Page 2: ...hnology and be protected from overload at all angles of rotation Actuators shall have reversing switch and manual override on the cover Actuators with auxiliary switches must be constructed to meet the requirements for double insulation so an electrical ground is not required to meet agency listings Run time shall be constant and independent of torque Actuators shall be cULus listed have a 5 year ...

Page 3: ... Loading and Actuator Sizing Damper torque loadings used in selecting the correct size actuator should be provided by the damper manufacturer If this information is not available the following general selection guidelines can be used Damper Type Torque Loading Opposed blade without edge seals for non tight close off applications 3 in lb sq ft Parallel blade without edge seals for non tight close o...

Page 4: ... instructions A B C D LMQB to 1 05 to 1 6 to 7 ft lb NMQB to 1 05 to 1 6 to 7 ft lb AMQB to 1 05 to 1 6 to 7 ft lb LMQB NMQB and AMQB clamps have an insert that self centers on the following diameter shafts default and 1 05 Shorter with reversible clamp for AM 2 1 1 65 1 2 1 2 5 1 0 D 2 1 1 2 3 4 5 ...

Page 5: ...clamp to about 5 from the closed position to between stop and clamp Tighten the two nuts on the universal clamp with a 10 mm wrench see table for required torque 5 Snap on the reflective position indicator Adjust end stops if required 6 Mount actuators indoors If mounted outdoors use approved protective enclosure The damper is now fully closed but the actuator is 5 from fully closed This is called...