background image

Technical data sheet

H6..SP

Globe valve, partial pressure relief, 

2-way, Flange, PN 16

•  For closed (high temperature) hot 

water and steam systems in the non-

critical range

•  For water-side modulating control of 

air-handling and heating systems

Type overview

Type

DN

[ ]

kvs

[ m³/h]

Stroke

[ mm]

PN

[ ]

Sv min.

[ ]

H640SP

40

25

15

16

100 

H650SP

50

40

15

16

100 

H664SP

65

58

18

16

100 

H679SP

80

90

18

16

100 

H6100SP

100

145

30

16

100 

H6125SP

125

220

40

16

100 

H6150SP

150

320

40

16

100 

 

Technical data

Functional data

  Media

Hot water and steam ( ∆p/P1 <0.4), water with 

max. 50% volume of glycol

 

Medium temperature

5...150°C

 

Medium temperature note

120°C up to 1600 kPa

150°C up to 1400 kPa

 

Permissible pressure ps

1600

 kPa

 

Flow characteristic

equal percentage (VDI/VDE 2173) n(gl) = 3, 

optimised in the opening range

 

Leakage rate

max. 0.05% of the kvs value

 

Pipe connectors

Flange according to ISO 7005-2 (PN 16)

 

Closing point

Bottom (▼)

 

Installation position

Upright to horizontal (in relation to the stem)

 

Maintenance

Maintenance-free

Materials

 

Housing

EN-JL1040 (GG25), with protective paint

 

Closing element

Stainless steel

 

Stem

Stainless steel

 

Stem seal

PFTE V-ring

 

Seat

Stainless steel

Safety notes

!

•  The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and is not allowed to be used outside the specified field of 

application, especially in aircraft or in any other airborne means of transport.

•  Only authorised specialists may carry out installation. All applicable legal or 

institutional installation regulations must be complied during installation.

•  The valve does not contain any parts that can be replaced or repaired by the user.
•  The valve may not be disposed of as household refuse. All locally valid regulations 

and requirements must be observed.

•  When determining the flow rate characteristic of controlled devices, the recognised 

directives must be observed.

www.belimo.eu

H6..SP • en-gb • 2014-11-27 • subject to changes