9.6 Outputs
9 Technical data
9.6 Outputs
Each channel can independently switch 2.0 A, the port groups X1/X2, X3/X4,
X5/X6, X7/X8 can each support a total load of 6.5 A at their 4 channels. The
complete port group X1…X8 can support a max. load of 9 A.
Output connection
Nominal output current per channel:
Type 2.0 A as per IEC 61131-2
See information 1
Signal status “1”
Signal status “0”
Max. 2.0 A
Max. 1.0 mA (standard specifications)
Signal level of the outputs:
Signal status “1”
Signal status “0”
Min. (U
L
– 1 V)
Max. 2 V
Short-circuit protection
Yes
Max. output current per module
0980 ESL 3xx-111…:
As per U
L
approval: 9 A (12 A see info 2)
0980 ESL 3xx-121…
As per U
L
approval: 9 A (16 A per supply point)
Overload proof
Yes
Number of digital channels
0 with 16 DI
16 with 16DO
8 with 8DI/8DO
16 with DIO
Channel type
Normally open, p-switching
Status indicator
Yellow LED per channel A
White LED per channel B
Diagnostic indicator
LED red per channel
Port
M12 socket, 5-pin
See pin assignment
Table 73: Release notes on the outputs
Manual LioN-P EtherNet/IP
Version 2.0 11/2017
94