Technical data
100
11.5 IO-Link master ports (X1-X8, Ch.
A/C/Q/ Pin 4)
Technical manual LioN-P PROFINET IO-Link Master
Release 2.0 04/2017
11.5.2 Configured as a digital output
(except 0980 ESL 308-121)
11.5.3 Configured as an IO-Link port in COM mode
NOTE
Power is supplied to the 500 mA outputs via the U
s
power supply.
Output type
Normally open, p-switching
Nominal output current per channel
Signal status “1”
Signal status “0”
500 mA (for UL application 400 mA)
Max. 500 mA
Max. 1 mA
Signal level of the outputs
Signal status “1”
Signal status “0”
Min. (U
S
-1 V)
max. 2 V
Max. output current per device
16 A (M12 Power) (for UL application 9 A)
6 A (M12 Hybrid)
Short-circuit/overload protected
yes/yes
Behavior in case of short circuit or overload
Disconnection with automatic power on
Number of digital outputs
LioN-P 30: max. 8 (Pin 4)
LioN-P 60: max. 8 (Pin 4) + 4 (Pin 2)
Status indicator
LED yellow per output
Diagnosis indicator
Red LED per channel
Table 47: IO-Link master ports configured as digital outputs
IO-Link master specification
v1.1, IEC 61131-9
Communication rates
4.8 (COM 1), 38.4 (COM 2) and 230.4 kbaud
(COM 3)
Line lengths in the IO-Link device
max. 20 m
Number of IO-Link ports (type A/type B)
8
Number of type A ports (X1, X2, X3, X4)
4
Number of type B ports (X5, X6, X7, X8)
4
Table 48: As an IO-Link port in COM mode