Starting operation
Technical manual LioN-Link BusHead EtherNet/IP™
Release 1.1 04/2016
5.3 IP address
27
The following settings are possible via the rotary encoding switch:
Rotary switch setting
Function
000
(state on delivery)
In the state on delivery, the DHCP function is activated. The
module first requests the network parameters via DHCP. The
network parameters are not saved, but the integrated web server
can be used to save them.
000
(network parameters
already saved)
The module uses the last network parameters that were saved (IP
address, subnet mask, gateway address, DHCP on/off, BOOTP
on/off).
001 to 254
The module overrides the last 3 digits of the stored or preset IP
address setting via the rotary encoding switch.
255 to 998
(exception: 888)
The module requests the network parameters via DHCP or
BOOTP, but does not save the network parameters.
888
The module resets to the factory settings. The network parameters
are reset to their default values. Communication is not possible in
this operation mode. The LioN Link configuration and the user
settings are also reset.
999
The module uses the IP address (
192.168.1.1
) as a factory
default.
Table 7:
Setting options for the rotary encoding switch