LDX-L30 Series

 

2

 

 

 

 

[email protected] 

 

 

 

USER INSTRUCTIONS

 

DESCRIPTION

 

DIN rail mountable Settable sealed Lead Acid Battery dual voltage housing. 

INSTALATION

 

Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device 
is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3). 

CONNECTIONS

 

The device is equipped with pluggable screw terminals. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power 
and waited for internal capacitors discharge (minimum 1 minute) 
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of: 
60°C for ambient up to 45°C 
75°C for ambient up to 60°C 
90°C for ambient up to 70°C 
Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5) 

INPUT PROTECTION

 

The device input is provided with polyswitch against overcurrent. 

DC INPUT / OUTPUT CONNECTION

 

Connect 

BATT. +

 terminal to + pole, 

BATT. -

 terminal to - pole.  

The device is suitable for 

SELV

 and 

PELV

 circuitry. 

WARRANTY

 

Battery pack are guaranteed free from factory defects for the time specified in the “Sales Conditions”

 

Failures caused by misuse, external and/or abnormal events (i.e. overvoltage, over temperatures) or non-respect of above parameters and standards, are not covered by 
warranty. Opening the housing of the product makes warranty to be no longer valid. 

BATTERY

 

Please pay attention, 

the batteries are not included

, we recommended to use batteries with final dimension (W x H x D) 48.5 x 54.5 x 97.5 mm Max terminals included. 

 

 
 
 

FIG.1 - CONNECTIONS 

FIG.2 - DIMENSIONS 

FIG.3 - DISTANCES 

 

 

(1)

 

Battery Connection 

(2)

 

Place wire Jumper to Set 24 VDC /1.2 Ah 

(3)

 

Place wire Jumpers to Set 12 VDC /2.4 Ah 
 

 

 

 

 

Attention! 
Do  not  Set  the  configuration  2  and  3  at  the 
same time.

 

Dimension 


mm (inc) 

54 (2.12) 

110 (4.33) 
115 (4.52) 

Distance 


mm (inc) 

20  
20 

 

 

Summary of Contents for LDX-L30

Page 1: ...capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühlen des Gerätes bevor Sie es berühren Lassen Sie keine Flüssigkeiten oder Fremdkörper in die Geräte eindringen Um Überschläge zu v...

Page 2: ...the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection see Fig 5 INPUT PROTECTION The device input is provided with polyswitch against overcurrent DC INPUT OUTPUT CONNECTION Connect BATT terminal to pole BATT terminal to pole The device is suitable for SELV and PELV circuitry WARRANTY Battery pack are guaranteed free from factory defects ...

Page 3: ...intaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 DISMOUNTING 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 Unhook the unit from the rail 1 2 3 F...

Page 4: ...polarity The colored wires should respect the bending as indicated in the diagram on side Attention Do not stress mechanically the cables After connecting the wires on the batteries and after having placed the batteries in the enclosure the LDX L30 should appear as on the picture above FIG 7 ENVIRONMENT BATTERY SETUP Attention Do not use Jumper 1 when Jumper 2 and 3 are connected FIG 8 ENVIRONMENT...

Reviews: