LDN481 Series

 

2

 

 

 

 

[email protected]

 

belfuse.com/power-solutions

 

 

USER INSTRUCTIONS

 

1) DESCRIPTION 

DIN rail mountable primary switching mode power supply with 90 

 132 VAC 

if the“120

 VAC 

Voltage Sel. Bridge”

 i

s connected,

 and 187 

 264 VAC if the 

“120

 VAC 

Voltage Sel. Bridge”

 

is not connected

; 270 

 345 VDC input if 

the “120

 

VAC Voltage Sel. Bridge”

 

is not connected

, suitable for single phase main line and DC line.

 

2) INSTALLATION 

Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device 
is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).  
The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping. 
The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce 
the load (see Fig.8) 

3) CONNECTIONS

 

The device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power and 
waited for internal capacitors discharge (minimum 1 minute) 
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of: 
60°C for ambient up to 45°C 
75°C for ambient up to 60°C 
90°C for ambient up to 70°C 
Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5) 

4) INPUT PROTECTION

 

The device input is provided with varistors against overvoltage. Input is provided with internal fuses 6.3AT / 250 VAC, thus an external short circuit / overcurrent protection 
must be provided by the end user (see Fig.6). 
For operation on a single-phase system, a protection fuse on the phase must be provided.

 

Surge protection:

 it is strongly recommended to provide external surge arresters (SPD) according to local regulations. 

5) AC INPUT CONNECTION

 

The device can be connected to single phase AC line with rated Vin 120 or 240 VAC (see Fig.7). Please connect first the PE. 

Need attention, set correctly the Input “120

 

VAC Voltage Sel. Bridge” based on the 

input voltage used.

 

6) DC INPUT CONNECTION 

Connect L terminal to (+) positive pole, N terminal to (-) negative pole and  

terminal to GND. Rated voltage 270 

 345 VDC. 

Need attention, do 

not connect the Input “120VAC Voltage Sel. Bridge” when it use in 

DC. 

The device is also suitable for photovoltaic or wind turbine applications (see Fig.7). 

7) OUTPUT CONNECTION 

The device is suitable for 

SELV

 and 

PELV

 circuitry. Pay attention LDN481-72 is not 

SELV

. Vout can be adjusted with a potentiometer to a wide range (see Fig.1) 

Check Vout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal 
power. 

8) PARALLEL CONNECTION AND REDUNDANCY

 

Power supplies can be connected in parallel to increase power. For paralleling for power set the Ilim jumper to C.C. algorithm. 
Vout must be set uniformly (±100 mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution. 
For redundant connection, use an external isolating device must be used (see accessory device). 

9) OUTPUT PROTECTION 

The device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT). 

OL and SC:

 are controlled by a hiccup mode or a constant current (C.C.) mode protection with the following behaviour. 

The Hiccup mode or C.C. mode are selectable with Jumper (see Fig.1) 
OL behaviour in hiccup mode:

 max. OL = 1.5 x In the output voltage remains constant at nominal voltage for about 5 s and after that time the device starts an ON/OFF 

cycle. 

OL behaviour in CC mode:

 max. OL = 1.5 x In the output voltage remains constant at nominal voltage for about 5s and after that time the device limits the current at In. If 

the load resistance is further decreased the output voltage starts to drop. The device never switches OFF. 

SC behaviour in hiccup mode: 

the device supplies 1.5 x In for about 5s and after that time the device starts an ON/OFF cycle.

 

SC behaviour in CC mode:

 the device supplies 1.5 x In and the output voltage drops to a level depending on the impedance of the failed load circuit. After 5s the current 

is limited to In. The device never switches OFF. 

Output OV circuit protection: the output is protected against potential OV due to internal malfunction or coming from the load for Vout 

 

V

nom x 1.2…1.4, 

depending on 

the model.

 

OT protection:

 turns off the device if the internal temperature exceeds a safe limit. 

The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase cooling or reduce 
load (see Fig.8). 

10) FEEDING DC MOTORS 

It is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can trigger 
overcurrent protection (see accessory device). For these applications the C.C. (Constant Current) mode of current limitation is recommended. 

NOTE:

 Motors can generate high conducted noise on the DC line. Therefore it is not recommended to feed on the same line motors and equipment sensitive to noise. 

11) OPERATION WITH BATTERY 

When a battery is connected in parallel to the Output for backup purposes; the LDN481 must be set on C.C. mode to avoid battery over-charging 
(see accessory device). 

 

 

Summary of Contents for LDN481 Series

Page 1: ...liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse de...

Page 2: ...or SELV and PELV circuitry Pay attention LDN481 72 is not SELV Vout can be adjusted with a potentiometer to a wide range see Fig 1 Check Vout before connecting the power supply to the load With output voltage set to the max value the continuous current x voltage must not exceed the nominal power 8 PARALLEL CONNECTION AND REDUNDANCY Power supplies can be connected in parallel to increase power For ...

Page 3: ...tive DC Earth ground Output Positive DC Negative DC Dry contact NC Dimension W D H mm inc 80 3 15 137 5 5 41 127 5 00 Distance A B mm inc 20 0 8 100 3 9 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as sp...

Page 4: ...ers SPD according to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 45 C 7 2 W C over 45 C NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of the Installation Instruction for each product by visiting belfuse com power solu...

Reviews: