Technical description
30
DRYPOINT® RS 15-550 HP50 NA
11.19.5 How is controlled the condenser fan
A pressure probe BP2 is located on the discharge side of the compressor. The condenser fan is activated (ON) when
the BP2 pressure is higher than FANon setting (R134a approx. 11 barg/160 psig
– R407C approx. 18 barg/260 psig) and
led
is ON. Condenser fan stops when BP2 pressure is lower than FANoff setting (R134a approx. 8 barg/115 psig
– R407C approx. 14 barg/203 psig).
11.19.6 How is controlled the drain solenoid valve
Drain solenoid valve is activated (ON) for
seconds (standard 2 seconds) every
minutes (standard 1 minute).
Led
shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button
.
NOTE :
if an electronic drainer is installed, DMC34 is set to keep always powered the drain output (
= ON).
11.19.7 How to reset the service reminder timer
With dryer OFF keep pressed buttons
+
, power the dryer and switch it on using the ON-OFF
switch (pos.1 paragraph 7.1).
After 5 seconds display shows
, release buttons
+
, keep pressed button
for 5
seconds. Timer has been reset and controller start to operate regularly.
Service reminder timing can be reset at any time, even before the timing has expired.
11.19.8 Operation of the failure / alarm dry contact
The DMC34 is equipped with a dry contact (potential free) to display failure and/or alarm conditions.
Dryer powered and no service warning / alarm is active.
Dryer not powered or service warning / alarm is active.
11.19.9 How to change the operating parameters
The setup menu can be used to
change the dryer’s operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON simultaneously press buttons
+
for at least 5 seconds to enter the setup menu.
Access to the menu is confirmed by message
on the display (first parameter of menu).
Keep
pressed to display the value of the selected parameter and use arrows
and
to
change the value. Release the button
to confirm the value and skip to following parameter.
Press
+
to exit setup menu (if no button is pressed after 2 minutes the menu is exited
automatically).
ID
Description
Limits
Resolution
Standard
setup
Ton
– drain time ON : time ON condensate drain valve
ON = Electronic drainer installed
ON
00 … 20 sec
1 sec
2
ToF - drain time OFF : pause time for condensate drain valve
1 … 20 min
1 min
1
HdS
– High DewPoint Setting : Alarm threshold for a high
DewPoint (the alarm disappears when the temperature drop
1°C / 2°F below alarm point)
0.0…25.0 °C
or
32 … 77 °F
0.5 °C
or
1 °F
20
or
68
Hdd - High DewPoint Delay : high DewPoint alarm enable
delay
01 … 20
minutes
1 min
15
SrV - Service Setting: setting of service warning timer.
00 = service warning timer disabled.
00.0
… 20.0
(x 1000) hours
0.5
(x1000)
hours
08.0
SrC
– Service Contact : configuration of the alarm dry contact
for the service warning timer.
YES = activate the contact / NO = NOT activate the contact
YES / NO
-
YES
SCL - Scale: display scale of temperatures and pressure (°C
= temperatures in °C and pressure in barg; °F = temperatures
in °F and pressure in psig)
°C … °F
-
°C
Set
Set
8
9
8
9
Set
Set
Set
Summary of Contents for DRYPOINT RS 100-E HP50 NA
Page 22: ...22 DRYPOINT RS 15 550 HP50 NA 10 4 Technical data DRYPOINT RS 180 550 3phase HP50 NA 3 380 60 ...
Page 40: ...Appendices 40 DRYPOINT RS 15 550 HP50 NA 13 1 2 Dryer dimensions DRYPOINT RS 50 80 HP50 NA ...
Page 41: ...Appendices DRYPOINT RS 15 550 HP50 NA 41 13 1 3 Dryer dimensions DRYPOINT RS 100 140 HP50 NA ...
Page 42: ...Appendices 42 DRYPOINT RS 15 550 HP50 NA 13 1 4 Dryer dimensions DRYPOINT RS 180 350 HP50 NA ...
Page 43: ...Appendices DRYPOINT RS 15 550 HP50 NA 43 13 1 5 Dryer dimensions DRYPOINT RS 450 550 HP50 NA ...
Page 47: ...Appendices DRYPOINT RS 15 550 HP50 NA 47 13 2 2 Exploded diagram DRYPOINT RS 15 40 HP50 NA ...
Page 48: ...Appendices 48 DRYPOINT RS 15 550 HP50 NA 13 2 3 Exploded diagram DRYPOINT RS 50 80 HP50 NA ...
Page 49: ...Appendices DRYPOINT RS 15 550 HP50 NA 49 13 2 4 Exploded diagram DRYPOINT RS 100 140 HP50 NA ...
Page 59: ...Appendices DRYPOINT RS 15 550 HP50 NA 59 13 3 2 Electric diagram DRYPOINT RS 15 40 HP50 NA ...
Page 60: ...Appendices 60 DRYPOINT RS 15 550 HP50 NA 13 3 3 Electric diagram DRYPOINT RS 50 80 HP50 NA ...
Page 61: ...Appendices DRYPOINT RS 15 550 HP50 NA 61 13 3 4 Electric diagram DRYPOINT RS 100 140 HP50 NA ...
Page 62: ...Appendices 62 DRYPOINT RS 15 550 HP50 NA 13 3 5 Electric diagram DRYPOINT RS 180 260 HP50 NA ...
Page 63: ...Appendices DRYPOINT RS 15 550 HP50 NA 63 13 3 6 Electric diagram DRYPOINT RS 350 HP50 NA ...
Page 64: ...Appendices 64 DRYPOINT RS 15 550 HP50 NA 13 3 7 Electric diagram DRYPOINT RS 450 550 HP50 NA ...
Page 71: ...DRYPOINT RS 15 550 HP50 NA 71 ...