CHECK the integrity of the probe after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result of which BEINAT
S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals or objects.
TERMS and EXPECTATIONS: The installation of the BX308xp, its ordinary and extraordinary maintenance, and its
out of service removal at the end of the functional life guaranteed by the manufacturer, must be carried out by
authorized and/or specialized personnel.
Do not allow it to become wet.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the probe could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Absolutely avoid using any cloth dipped in thinners, alcohol and chemical detergents.
Disposal of the device
Concerning the conservation, the protection and the improvement of the quality of the environment, as well as for the
protection of human health and the careful and rational use of natural resources, the device has to be the object of
a selective collection for he disposal of electronic equipments and can not be disposed with the common domestic waste.
The user thus has the obligation to separate the device of the other waste to ensure that it is recycled in a sure way
for preserving the environment For more details on the sites that are involved in the collection, contact the local
administration or the distributor of this product.
Useful Information
Main Compatible Probes
MAINTENANCE
The user periodically (every 6 months) must perform a check of the operation of the control unit by spraying
a suitable test gas at the base of the probes connected until the alarm condition is reached.
• At least once a year make a more accurate check by a specialist technician.
• Disabling the detector must be carried out by qualified personnel.
The installation of the gas detection system does not exonerate. From the observance of all the rules regarding the
characteristics, the installation and the use of the gas appliances. The ventilation of the premises and the discharge of the
combustion products prescribed by the UNI standards as per ART. 3 LAW 1083/71 and the relevant provisions of law.
SG500
Catalytic
IP30
Domestic Use
CH4-LPG
0÷100% LEL 4÷20 mA
±5 %
NO
NO
SG544
Catalytic
IP44
Tertiary
CH4-LPG
0÷100% LEL 4÷20 mA
±5 %
NO
NO
SGM595
Catalytic
IP55
Tertiary
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
NO
SGM595/A
Catalytic
IP66
Zone 2
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
NO
SGM533
Catalytic
IP55
Tertiary
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
SG800
Catalytic
IP66
Zone 2
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
HCF100
SemiCondut
IP55
Tertiary
FREON
0÷300% ppm 4÷20 mA
±5 %
NO
Yes
SG895
Pellistor
ATEX
Zone 1
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
NO
SG580
Catalytic
IP66
Zone 2
See catalogue
0÷100% LEL 4÷20 mA
±5 %
Yes
NO
SGF100
Catalytic
IP64
Zone 2
Methane
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
SGF102
Catalytic
IP64
Zone 2
LPG
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
SGF104
Optical Fluores
IP64
Zone 2
Oxygen
In %
4÷20 mA
±5 %
Yes
Yes
SGF106
SemiCondut
IP64
Zone 2
FREON
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
SGF108
Elettrochimica
IP64
Zone 2
H2S
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
SGF110
Electrochemical
IP64
Zone 2
C O
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
SGF112
Catalytic
IP64
Zone 2
Hydrogen
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
CO100r
Electrochemical IP55
Tertiary
C O
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
CO100Ar
Electrochemical IP66
Zone 2
C O
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
SG800
duct
Catalytic
IP66
Zone 2
CH4LPG
0÷100% LEL 4÷20 mA
±5 %
Yes
Yes
CO200
duct
Electrochemical IP66
Zone 2
C O
0÷300% ppm 4÷20 mA
±5 %
Yes
Yes
Application in:
Domestic: family accommodation. Local boilers up to 70 kW-h
Tertiary Areas: Large Rooms Boilers, Workshops, Material Deposits, Industrial Kitchens, Large Buildings, Buildings.
Zone 2 - Mixed IP66 ATEX: High probability of escape, high risk locations, premises for which applicable regulations apply.
Zone 1 - Hazardous Area, High Risk Hazards, Rooms for Which Regulations, Tanks, Control Valves are in force.
Probe
Sensor Degree Suitable for
Gas
Range Output Precis. Calibration Relay
Protec. Detected Working Automatic
Sensor