BEINAT BX308xp Installation And User Manual Download Page 14

Page  14

30 cm Light Gases

30 cm Heavy Gases

Middle Height Volatile Gases

    PROBE  INSTALLATION  INFORMATION

Installation  and  positioning  of  the  probe

The BX308xp control unit belongs to group II and must be installed in a safe area;

Outside the ATEX zone

, however, not in boiler rooms or engine room.

The control unit must be accessible and visible to the user.

The BX308xp has an Omega Bar enclosure and is a device suitable for mounting on pre-assembled quads and has IP20
protection. powered at 15 VDC
The BX308xp / boxed complete cabinet is an equipment suitable for wall mounting and is powered by 110/240 VAC
with IP65 protection

When installing, it is good to use the normal care that an electronic equipment requires:
- Install the equipment away from excessive heat sources.
- Avoid liquids coming into contact with the control unit, remembering that its external structure has IP20 degree of
protection if installed on the Boxed version (cabinet) supplied to the source is IP65.

The probes must be selected with an IP degree depending on the area to be controlled (Kitchens, Boiler
Rooms, Laboratory, etc.) by selecting one of the probes from Beinat from IP30 to ATEX. 
see page 3

Position of the detection probes

You can connect many types of remote probes to this unit. Therefore, they should be positioned at different heights
depending on the type of gas to be detected.

These heights are:
- 30 cm from the lowest point of the floor in order to detect:

Heavy gases (L.P.G. etc.)

- 30 cm from the highest point of the ceiling in order to detect:

light gases (Methane, etc.)

- 160 cm from the lowest point of the floor in order to detect:

volatile gases (CO, etc.)

It is important to note that the remote probes should be installed according to the following restrictions:

1) The probes should not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.)
but on the opposite side.
2) The probes should not be affected by smoke, vapour, and moving air, as they could distort their measurement.
3) The probes should not be placed near sources of heat, ventilators or fans.
It should be noted that the internal GAS sensors of the probe are perishable components with a variable average
life span from 5 to 6 years (you can request the relative table). Therefore, after this period of time has elapsed it
is advisable to replace them.
4) The control of operation and maintenance  and / or extraordinary must be carried  at least once a year. good
to keep
When turning on leds fault is necessary make the replacement of the probe by a specialized technician.

Summary of Contents for BX308xp

Page 1: ...le and innovative using With conventional sensors Up to 8 remote probes Conventional from 4 to 20 mA can be connected in conventional mode for a single zone Gas concentration measured by every probe sequentially is shown directly on display with a description of its origin When one of the coupled probes exceeds the pre alarm setpoint the control unit generates a proportional sound signal depending...

Page 2: ... 7 V 10 Battery Charger Max 2 2 Ah controlled Max power demand in alarm with 8 probes connected 15W Max 12 V Max power demand in alarm with 8 probes connected 19W Max 240VAC Relay Contact Range 10A 250V resistive ALARMS 1st Pre Alarm adjustable for every probe from 3 450ppm to 16 240ppm of L E L 2nd Final alarm for every active area set to 20 of LEL or 300 ppm CO Monitored Gas Indication Through i...

Page 3: ...st technician Disabling the detector must be carried out by qualified personnel The installation of the gas detection system does not exonerate From the observance of all the rules regarding the characteristics the installation and the use of the gas appliances The ventilation of the premises and the discharge of the combustion products prescribed by the UNI standards as per ART 3 LAW 1083 71 and ...

Page 4: ...D turns on and flashes when one of the probes coupled is damaged or the connection cables are interrupted or there is a connection error When this LED is turned on the equipment can no longer detect the gas and it activates the relays of both threshold levels the 1st and the 2nd To restore operation the probe must be repaired or removed by pressing RESET using the setting program 2 Alarm LEDS a PR...

Page 5: ...correct you will see Password accepted If you made a code input mistake you will see Wrong password You should re enter the password If you do not press any key you will return to the previous screen DATE and TIME SETTING Use the Left and Right buttons to select Time Setting and press ENTER You will access the current date and time setting program PROBE SETTING Use the Left and Right buttons to se...

Page 6: ... 1 each time you press the ENTER button a rectangle will appear with the text Activation deactivation of probes and type of gas selection Explosive or Toxic Press DOWN to get probe 1 blinking Now each time you press ENTER you will get the following box E you have enabled a probe for explosive gas T you have enabled a probe for toxic gas O you have enabled a probe for oxygen gas you have disabled t...

Page 7: ...se T On the first line you will see the gas percentage of 150 ppm To change the percentage press ENTER The percentage is increased each time of 15 ppm starting from 45 ppm up to a maximum of 240 ppm The percentages are increased cyclically Probe Setting continue 1 2 3 4 5 6 7 8 T T O E T T T T T E E E E Configurazione sonde Oxygen Gas Setting pre alarm main alarm Key Oxygen depletion Oxygen excess...

Page 8: ...eep in mind that when this operation is peformed the relative probes must also be setted to the same range Select the top right arrow and press ENTER to return to the previous program Due to the sheer importance of this operation any change to the operative range shall be confirmed END to the exit program select the Back Arrow Probe Setting continue Giù Sù SX DX ENTER Setting the Percentage of Pre...

Page 9: ...lation you can select the relay functioning mode The relay functioning modes are two continuous and impulse In the Continuous position the relay remains closed until the alarm status continues or until the alarm stops In the Impulse position the relay remains closed for 20 seconds and then disenergizes afterwards Selection Use the UP and DOWN buttons to select Relay Each time you press ENTER the C...

Page 10: ...Silent Mode The BX308xp program allows the silent mode for the external siren The siren could be annoying during test phases or extensive alarms The silencing is indicated by a red LED on the front panel Red LED on means siren silenced Red LED off means siren working Selection Use the UP and DOWN buttons to select Siren Silent Mode Each time you press ENTER the ON OFF message is changed In the ON ...

Page 11: ...be Enabled Probe Disabled Hard Reset Event 06 Retrieving data Event 05 Retrieving data Event 02 Retrieving data Event 04 Retrieving data Event 03 Retrieving data Event 01 Retrieving data Event 06 25 Lug 13 08 15 Low Battery Vbatt 03 3 V Event 05 24 Lug 13 09 15 Reset Event 01 24 Lug 13 15 28 Probe 16 Pre Alarm V 02 6 V I 17 3 mA Event 02 24 Lug 13 15 28 Probe 12 Alarm V 02 6 V I 17 3 mA Event 03 2...

Page 12: ...bes use the RIGHT and LEFT buttons to reach the desired probe General Functions continue Giù Sù SX DX ENTER Print status Print datalogger 1 2 3 4 5 6 7 8 T T T E E 1 2 3 4 5 6 7 8 T T T T E E E E Zone 1 Zone 2 V 3 2 I 20 2 mA BEINAT BX308 xp Ver 1 0 S N Sample Serial number 0102 Date Hour 07 oct 17 10 00 State probes Probe 01 Zone 1 Gas Type Explosive Gas Level 02 9 LEL Meas Current 06 2 mA Status...

Page 13: ... code CARD RLS4 On each card there are 4 relays which can be associated with the desired probes range Each relay may be assigned to one of the following functions Pre alarm Alarm Fault or Not Used Each relay may be assigned a range of probes from 1 to 16 Display CARD RLS4 Indicates the hardware address set in the card read information To change the current expansion card press ENTER The expansion ...

Page 14: ... 3 Position of the detection probes You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the low...

Page 15: ... fitted with protection fuses 2 You will notice that some LEDs will light up in turn for about 20 seconds 3 The display will start the COUNT DOWN of about 90 seconds warm up At the end the control unit is ready for detection 4 Pressing and holding down the TEST button you can obtain a gas leakage simulation The control unit will carry out the following It will light up the 13 LEL or the 200ppm wit...

Page 16: ...L3 Green led voltage switched Yellowled transmission Tens Unit Example to select an address Turn the Switch of tenths until you find the desired tenth For example 0 Turn the Switch of units until you find the desired unit For example 6 In this way you will set the address 6 Eachconnectedboardmust havean address unique to avoid conflicts in the data transmission To enter the addresses of each CARD ...

Page 17: ...larm Exit Alarm SirenStatus Test Reset C NC NO C NC NO Prealarm Main Alarm 1 2 3 4 5 C NC NO C NC NO Fault Sirena Ext 6 7 8 9 Manual alarm PAM NC 1 2 3 4 5 6 7 8 3 2 1 Sonda 1 3 2 1 Sonda 2 3 2 1 Sonda 3 3 2 1 Sonda 4 3 2 1 Sonda 5 3 2 1 Sonda 6 3 2 1 Sonda 7 3 2 1 Sonda 8 15VDC Characteristics standard switching power supply 230 VAC 15 N B Power supply included in the box version Cards Relay Conv...

Page 18: ...ctions Connecting a solenoid valve Normally Closed without Positive Safety C NC NO C NC NO C NC NO C NC NO 1 2 3 4 5 6 7 8 9 NA NC Power supply Switching Ph N 12 VDc Power supply 110 240 VAC Solenoid valves Prealarm Fault Siren ext Ph N 230 VAC C NO C NO C NC NO C NC NO 1 2 3 4 5 6 7 8 9 Solenoid valve Prealarm Fault Siren ext NC Ph N C NC NO C NC NO C NC NO C NC NO 1 2 3 4 5 6 7 8 9 Solenoid valv...

Page 19: ...ound and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you ha...

Page 20: ...INAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling ...

Reviews: