Page 13
Select “Factory Reset”. Pressing “ENTER” the message starts blinking.
By holding the “ENTER” button for 4 seconds, you will view a frame with 10 empty rectangles that will gradually
fill. At the end, the BX308xp will be totally reset and a new countdown of 90 seconds will begin.
Use the arrow down to the right and press “ENTER” to return to the previous program
Factory Reset
Before proceeding be sure to want to do it, all previously set data will be
res eted.
Expansion cards
CARD-RLS4: 02 (Address card)
03,04.. 16
Relay: 01
02 03 04
Funct.:
NOT USED
PREALARM ALARM FAULT
Sonda: 01
02, 03, 04 ...16
General Functions (continue)
The control unit can be operate with up to 16 Expansion Relay cards (code: CARD-RLS4).
On each card there are 4 relays which can be associated with the desired probes range.
Each relay may be assigned to one of the following functions: Pre-alarm, Alarm, Fault or Not Used
Each relay may be assigned a range of probes from 1 to 16.
Dis play
CARD-RLS4- Indicates the hardware address set in the card (read information).
To change the current expansion card press “ENTER”. The expansion card address is pointed cyclically to the
next available.
Relay. Press “ENTER” to choose the relay, from 1 to 4, to be associated to a function.
Function. Press “ENTER” to choose the function of the selected relay between:
NOT USED – PRE-ALARM – ALARM - FAULT
PROBES. Use the “RIGHT” and “LEFT” buttons to select the field “from” or “to”. Press “ENTER” to choose
the probe belonging to the desired range.
To exit the program and save the changes, select “Return Arrow”.
Giù
Sù
SX
DX
ENTER
16/10/17
Factory Reset