BEINAT BX280 Installation And User Manual Download Page 3

Page  3

Main Compatible Probes

MAINTENANCE

The user periodically (every 6 months) must perform a check of the operation of the control unit by spraying

a suitable test gas at the base of the probes connected until the alarm condition is reached.

• At least once a year make a more accurate check by a specialist technician.

• Disabling the detector must be carried out by qualified personnel.

Installation  of  the  detector  does  not  exonerate.  From  the  observance  of  all  rules  regarding  the  characteristics,
installation and use of gas appliances. The ventilation of the premises and the discharge of the combustion products
prescribed by UNI norms as from ART. 3 LAW 1083/71 and the relevant provisions of law

.

SG500

Catalytic

IP30

Domestic  Use

CH4-LPG

0÷100% LEL      4÷20 mA

±5 %

NO

NO

SG544

Catalytic

IP44

Tertiary

CH4-LPG

0÷100% LEL       4÷20 mA

±5 %

NO

NO

SGM595

Catalytic

IP55

Tertiary

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM595/A

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM533

Catalytic

IP55

Tertiary

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SG800

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

HCF100

SemiCondut

IP55

Tertiary

FREON

0÷300% ppm     4÷20 mA

±5 %

NO

Yes

SG895

Pellistor

ATEX

Zone  1

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SG580

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGF100

Catalytic

IP64

Zone  2

Methane

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF102

Catalytic

IP64

Zone  2

LPG

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF104

Optical  Fluores

IP64

Zone  2

Oxygen

In  %

  4÷20 mA

±5 %

Yes

Yes

SGF106

SemiCondut

IP64

Zone  2

FREON

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF108

Elettrochimica

IP64

Zone  2

H2S

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF110

Electrochemical IP64

Zone  2

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF112

Catalytic

IP64

Zone  2

Hydrogen

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

CO100r

Electrochemical IP55

Tertiary

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

CO100Ar

Electrochemical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

SG800

duct

Catalytic

IP66

Zone  2

CH4LPG

0÷100% LEL        4÷20 mA

±5 %

Yes

Yes

CO200

duct

Electrochemical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

Application  in:

Domestic:  family  accommodation.  Local  boilers  up  to  70  kW-h
Tertiary  Areas:  Large  Rooms  Boilers,  Workshops,  Material  Deposits,  Industrial  Kitchens,  Large  Buildings,  Buildings.
Zone  2  -  Mixed  IP66  ATEX:  High  probability  of  escape,  high  risk  locations,  premises  for  which  applicable  regulations  apply.
Zone  1  -  Hazardous  Area,  High  Risk  Hazards,  Rooms  for  Which  Regulations,  Tanks,  Control  Valves  are  in  force.

Probe

Sensor          Degree     Suitable for

 Gas

  Range             Output          Precis.        Calibration  Relay

Protec.                           Detected        Working                                            Automatic

                Sensor

WARNING! Actions to be taken in case of alarm

Gas
1) P
ut out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide

or by an excess

or  deficiency  of  oxygen

Summary of Contents for BX280

Page 1: ...sensors the BX280 control unit has been designed and built according to European regulations to detect the presence of toxic and or explosive gas flexibly A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX280 is suitable for civil and industrial applications The BX280 control unit has two danger levels...

Page 2: ...tten on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible damages caused to people animals or objects IMPORTANT Do not test the device using the gas tap as this doe...

Page 3: ...SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2 CH4LPG 0 100 LEL 4 20 mA 5 Yes Yes CO200duct Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Y...

Page 4: ...he battery and the connection cables OVER LOAD BATTERY LED battery overload If this led turns on it means the battery is not connected properly or it has an anomalous voltage absorption Please check the battery and the connection cables 5 TEST BUTTON Pressing and holding down this button you can obtain a gas leakage simulation This way all pre alarm LEDs until the final alarm led will light up in ...

Page 5: ... the ON position the positive safety function is enabled The relay is energized after performing the step of waiting and switches when the BX280 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX280 goes into the mainl alarm Switch 2 Working mode of the relay and the main alarm In the OFF continuous position the relay remains closed u...

Page 6: ... 300 ppm Over Load Battery Probe Power Battery CO GAS RESET TEST Electrical Connections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicese...

Page 7: ... Solenoid valves Ph N 230 VAC NC NA Diode 1N 5406 Solenoid valve GAS and Sirens 12 VDC 12 V 3 2 1 Probe 1 3 2 1 Probe 2 R1 R2 1 2 3 4 5 6 Powersupply 230 12V If a 12Vdc solenoid valve which does not work well is connected to the BX280 Direct connection of 12VDC solenoid valves or sirens to the BX280 is not permitted An external power unit must always be used The BX280 M gives a max current of 50mA...

Page 8: ... 230 VAC 230 VAC Electrical Connections Connections to Positive Safety disabled and an external power supply for valve control and siren 12 V DC If a 12Vdc solenoid valve which does not work well is connected to the BX280 Direct connection of 12VDC solenoid valves or sirens to the BX280 is not permitted An external power unit must always be used The BX280 M gives a max current of 50mA ...

Page 9: ... they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO etc It is important to note that the remot...

Page 10: ... connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX280 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is present that ...

Page 11: ...Page 11 NOTE ...

Page 12: ... as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will hel...