Service warning
The eMMC wear can be suppressed via settings menu in Diagnostics application.
- This suppression is only active until device life time in CSD register is changed.
Note:
The service warning message can be suppressed for 7 days by checking the checkbox
and press OK.
4.3.5
Service warnings
•
Rapid flash wear warning
“The unit internal disk lifetime is rapidly decreasing. Please consult the
documentation how to reduce wear, or how to minimize it.”
Occurs when the user’s program is quickly decreasing the flash memory’s wear.
Consult the “X2 and iX Developer 2.40 – Flash memory best practice” guide
found under Resources for the unit’s product page on Beijer Electronics’
webpage.
•
Flash lifetime warning
“The unit should be scheduled for preemptive maintenance service. The internal
disk memory is soon reaching its expected lifetime.”
This warning appears when that the unit’s flash memory is reaching its
expected lifetime. The only solution is to replace the entire unit.
•
Battery warning
“The unit internal battery is due and needs to be replaced.”
Indicates the Real Time Clock (RTC) battery is depleted. This battery is used
by the system to power the internal clock and maintain a few stored settings.
The solution is to replace the 3V battery (CR 2032) with an equivalent one.
Warning: Opening the unit will void the warranty!
•
License warning
“Operating system license doesn’t match device type.
Occurs when the runtime version license running on the unit for Windows
Embedded Compact 2013 is incorrect. Contact support for solution.
Beijer Electronics, MAEN205G