Additional Installation Tips

A good solution may be to use a shielded Ethernet cable, but to connect the shield
at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernet cable, see 4 in drawing above.
The shield can be grounded via an external 0.1 μF/250 V film capacitor, see 5 in
drawing above. This connects the HF transients to ground.

7.3 To Achieve Better EMC Protection

Initially, use the original cabling from Beijer Electronics primarily.

Place the 24 V DC and communications cabling in one cable trunk/cable duct
and 230/380 V AC in another. If the cables need to be crossed, cross them at
90° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.

Initially, use the original cabling from Beijer Electronics primarily.

Use shielded cables for RS-232 communication.

Use twisted pair and shielded cabling for RS-422 and RS-485.

Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.

Use the cabling intended for the bus type; Ethernet and CAN

Install and connect according to applicable specifications for the relevant bus
standard.

Use shielded cabling for Ethernet, preferably with foil and a braided shield.

D-sub covers should be shielded, and the shield should be connected to the
cover 360° where the cable enters.

Connect the shield at both ends.

Shielded cable

Not same potential

Ground plane 1

Ground plane 2

Ground plate

Ground plate in another building

0.1 

μ

F/250 V

With longer distances, there is a risk that the ground potential may be different. In
that case, the shield should only be connected at one end. A good alternative is to
connect the other end of the shield to the ground via a 0.1 μF/250 V film capacitor.
Both ends are then connected to the ground in terms of HF, but only connected to
the ground at one end in terms of LF, thus avoiding the 50/60 Hz grounding loops.

Beijer Electronics, MAEN331

21

Summary of Contents for X2 base 10 v2

Page 1: ...X2 base 10 v2 English MAEN331 2021 05...

Page 2: ...l its group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only quali ed personnel...

Page 3: ...10 3 2 2 Other Connections and Peripherals 10 3 2 3 Open Ports 10 4 TechnicalData 11 5 ChemicalResistance 13 5 1 Touch Screen and Overlay Material 13 5 1 1 Protective Film 13 5 1 2 Touch Screen Surfac...

Page 4: ...me isotropic The LCDdisplay liquidcontainsa powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medica...

Page 5: ...se Keep the operatorpanel clean Emergency stopand othersafety functions may notbe controlled from the operator panel Do not use excessive force orsharpobjects when operatingthe touch screen 1 6 Servic...

Page 6: ...ouchscreen Do not use air guns water jets or steam to clean the surface of touchscreens as they may damage touchscreen functionality If condiments food or drinks are spilled on the surface of the touc...

Page 7: ...BL 12V SL RO CO web SoftControl SoftMotion High Brightness High performance Black 12 Volt Sealed Rugged Only Certification Only Examples X2 base 5 v2 X2 pro 7 X2 control 10 X2 marine 12 SC X2 marine 1...

Page 8: ...A Phillips slotscrewdriver Do the following 1 Unpackand check the delivery If damage isfound notify the supplier Note Place the operator panelon a stable surface duringinstallation Dropping the opera...

Page 9: ...r panel and the controller system have the same electrical grounding reference voltage level otherwise errors in communication may occur Ensure that the voltage and polarity of the powersource is corr...

Page 10: ...eripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier 3 2 3 Open Ports In the rmware there are some...

Page 11: ...erial Plastic Weight 0 84 kg CPU TI Sitara AM335x Single Core 600MHz TI AM3352BZCZ60 Serial port COM A Standard DSUB 9 pin female 1x RS232 RX TXwith RTS CTS 1x RS422 or 2x RS485 Serial port COM B N A...

Page 12: ...222 72 x 125 28 Pixel errors Class I ISO 9241 307 Backlight brightness 350 cd m2 Backlight lifetime 30000 hours Operating temperature 0 C 50 C Storage temperature 20 C 60 C Relative humidity in opera...

Page 13: ...owderin solution 1 Gumption 1 SBP 60 95 1 Bleach 1 Hydrochloricacid 36 Sulfuricacid 10 Castoroil Linseed oil Tomato ketchup Causticsoda 40 1 Methanol Trichloroacetic acid 50 Cuttingoil Nitric acid 10...

Page 14: ...uene 5 hours The touch screen surface on the operatorpanel is made of polyester with a hard coattoresistscratchesandwithstand exposure to manysolvents without visible change 5 1 3 Touch Screen Protect...

Page 15: ...2 0 Host max output current 500 mA 6 COM C screw Screw to connect COM C cable shield 7 COM C 3 pin screw connector COM A Serial port pin assignment Pin COM 1 COM 2 COM 3 1 RS422 TX or RS485 Tx Rx 2 RS...

Page 16: ...Operator PanelDrawings COM C Serial port pin assignment Pin COM 6 1 GND 2 RS485 Tx Rx 3 RS485 Tx Rx Beijer Electronics MAEN331 16...

Page 17: ...Operator PanelDrawings 6 2 X2 base 10 v2 Outline Note Minimum thickness for the frontplate is 2 0 mm Beijer Electronics MAEN331 17...

Page 18: ...Operator PanelDrawings Note A Step CAD file is available on the web site www beijerelectronics com Beijer Electronics MAEN331 18...

Page 19: ...t terminalconnectoron the operatorpanel and the chassis of the panel see 2 in drawing above 2 Connect awire orgroundingbraid that is sized correctlyaccording to local electrical codes betweenthe chass...

Page 20: ...5 RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 F 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45...

Page 21: ...RS 232 communication Use twisted pairandshielded cabling forRS 422 and RS 485 Use the cablingintendedforthe bus type Ethernet Pro bus CC Link CAN Device Netetc Use the cablingintendedforthe bus type E...

Page 22: ...ablingmayremove minor disturbances Large ferrite piecesthat are snapped ontounshielded cablingand where the wires go2 4 times around the cores are approximately 5 25 times more ef cient 7 4 Ambient Te...

Page 23: ...evens out the temperature while moving air providesconsiderably better coolingthan stillair Install the fan so that it sitsin a cooler area and blows coldairagainst the operator panel If the fan is mo...

Page 24: ...tion against electric shock and UL 950 Note Here is an example that explains why a secure 24 V DC powersupply can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller cont...

Page 25: ...nst the 24 V DC powersupply butnogalvanic isolation between the communication ports forRS 232 RS 422 RS 485 and USB Only the Ethernet connectionhas galvanic isolation The operatorpanel has galvaniciso...

Page 26: ...ngpoints there is a substantial risk of problems Groundingcurrents go through communication cables the rearplate of the controller internally in the operatorpanel and can cause errors Use external uni...

Page 27: ...ongerdistances or whenthere is adifference in the ground potential the shield should be connected tothe ground via 0 1 F 250 V lm capacitor toprevent ground current inthe braided shield Anumberof manu...

Page 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Reviews: