background image

INSTRUCTIONS

IMPORTANT SAFEGUARDS 

When using electrical equipment, basic safety precautions should always be followed including the following: 
1. 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

2.   Disconnect power before performing work on electrical equipment.
3.   Do not let power cords touch hot surfaces and do not mount near gas or electric heaters. 
4.   Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or  
 

eyes, flush with fresh water and contact a physician immediately. 

5.   Equipment should be mounted in locations and at heights where unauthorized personnel will not readily  
 

subject it to tampering. 

6.   The use of accessory equipment not recommended by Beghelli Canada Inc., may cause an unsafe condition,  
 

and will void the unit’s warranty. 

7.   Do not use this equipment for other than its intended purpose. 
8.   Servicing of this equipment should be performed by qualified service personnel. 
9.  

SAVE THESE INSTRUCTIONS! 

INSTALLATION

WALL MOUNTING:
1.  Remove mounting plate from fixture by prying with screwdriver. (See Figure 1)
2.  Insert screwdriver to make appropriate keyhole slots open on mounting plate.
3.  Pass white (neutral) and either black 120V or red 347V hot wire leads through center hole of mounting plate, make 

electrical connections in junction box, see electrical connection below. You may use hanging hook to hang fixture 
while making connection. Cap off unused hot lead.

4.  Mount mounting plate to junction box with screw provided 8#32x1” long.
5.  Connect red lead to battery positive terminal. (See Figure 2)
6.  Snap on fixture to mounting plate.
7.  Restore power and press test button. Battery powered bulbs will cone on. AC light will turn off.

CEILING MOUNTING:
1.  Remove mounting plate from fixture by prying with screwdriver gently. (See Figure 3)
2.  Open top cover and knockout on the top of fixture.
3.  Secure the mounting plate to tube with nut.
4.  Pass white (neutral) and either black 120V or red 347V hot wire leads through center hole of mounting plate. Make 

electrical connections in junction box, see electrical connections below. You may use hanging hook to hang fixture 
while making connection. Cap off unused hot lead.

5.  Connect red lead to battery positive terminal. (See Figure 2)
6.  Snap on fixture to mounting plate.
7.  Restore power and press test button. Batter powered bulb will come on. AC light will turn off.

ELECTRICAL CONNECTION:
Connect white wire lead from fixture to white (neutral) wire supply feed from circuit. Connect black 120V or red 347V, 
(depending on supply voltage), wire lead from fixture to black (hot) wire from supply circuit. Use ULC Listed wire 
connectors suitable for the size, type, and number of conductors. No loose strands or loose wires should be present. 
Secure wire connectors with ULC Listed electrical tape.

RELAMPING:
1.  Insert screwdriver into the slot between lens and light head body and then push gently to remove lens.
2.  Install lamp.