CURVA COMBO

NYC-CRV-C

 

AUTOTEST INSTRUCTION MANUAL

Page 1 of 2

Beghelli U.S.A., 3810 Executive Way, Miramar, Florida, Tel: (954) 442-6600

09/12/22

1.

Install the 

CURVA

 C

OMBO

 according to the installation

 

instruction

s

.

2.

When AC power is supplied to 

the unit

, the unit will automatically initiate a self-test

with 

self-diagnostic

s

 as follows:

(1) Monitors status of battery connection, charger board, lamps and transformer every 5

seconds.

(2) Performs a one-minute self-test every month.

(3) Performs a 30-minute self-test on the 6th month after installation.

(4) Performs a 90-minute self-test on the 12th month after installation.

Note: ALL functions are factory pre-set (does not need field adjustment).

3.

Dual color LED lamp indicator shows the following status:

(1)

Green color: ON/ Ready

Blinking: Testing

(2)

Red color: Service Alert
Blinking: Sequence below determines service required

One blink ON/pause

 

(4 seconds)

Battery is not connected

Two blinks ON/pause

 

(4 seconds)

Battery is shorted or battery voltage drops below acceptable level

Three blinks ON/pause

 

(4 seconds)

Charger board circuit fault

Four blinks ON/pause

 

(4 seconds)

Transfer circuit fault

Five blinks ON/pause

 

(4 seconds)

Emergency lamp fault

Six blinks ON/pause

 

(4 seconds)

Remote head’s emergency lamp fault (if fixture has remote capability)

Seven blinks ON/pause

Exit LED strip fault

TO RESET

:

After 

re

solving

 the fault of emergency equipment, press test button for 2 seconds without 

releasing to reset. 

 

LED indicator will show green.

4. For manual test, press test button as follows:

Press test button once

(within 2 seconds) 30

-

minute t

est

Press test button twice

 

(within 2 seconds)

3

-

minute test

Press test button 3 times (within 2 seconds) 30

-

minute test

Press test button 4 times (within 2 seconds) 90

-

minute test

(4 seconds)