CURVA COMBO
NYC-CRV-C
AUTOTEST INSTRUCTION MANUAL
Page 1 of 2
Beghelli U.S.A., 3810 Executive Way, Miramar, Florida, Tel: (954) 442-6600
09/12/22
1.
Install the
CURVA
C
OMBO
according to the installation
instruction
s
.
2.
When AC power is supplied to
the unit
, the unit will automatically initiate a self-test
with
self-diagnostic
s
as follows:
(1) Monitors status of battery connection, charger board, lamps and transformer every 5
seconds.
(2) Performs a one-minute self-test every month.
(3) Performs a 30-minute self-test on the 6th month after installation.
(4) Performs a 90-minute self-test on the 12th month after installation.
Note: ALL functions are factory pre-set (does not need field adjustment).
3.
Dual color LED lamp indicator shows the following status:
(1)
Green color: ON/ Ready
Blinking: Testing
(2)
Red color: Service Alert
Blinking: Sequence below determines service required
One blink ON/pause
(4 seconds)
Battery is not connected
Two blinks ON/pause
(4 seconds)
Battery is shorted or battery voltage drops below acceptable level
Three blinks ON/pause
(4 seconds)
Charger board circuit fault
Four blinks ON/pause
(4 seconds)
Transfer circuit fault
Five blinks ON/pause
(4 seconds)
Emergency lamp fault
Six blinks ON/pause
(4 seconds)
Remote head’s emergency lamp fault (if fixture has remote capability)
Seven blinks ON/pause
Exit LED strip fault
TO RESET
:
After
re
solving
the fault of emergency equipment, press test button for 2 seconds without
releasing to reset.
LED indicator will show green.
4. For manual test, press test button as follows:
Press test button once
(within 2 seconds) 30
-
minute t
est
Press test button twice
(within 2 seconds)
3
-
minute test
Press test button 3 times (within 2 seconds) 30
-
minute test
Press test button 4 times (within 2 seconds) 90
-
minute test
(4 seconds)