background image

IMPORTANT SAFEGUARDS 

When using electrical equipment, basic safety precautions should always be followed including the following: 

1.  READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

2.  Disconnect power before performing work on electrical equipment.
3.  Do not let power cords touch hot surfaces and do not mount near gas or electric heaters.
4.  Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or eyes, 

flush with fresh water and contact a physician immediately. 

5.  Equipment should be mounted in locations and at heights where unauthorized personnel will not readily subject it to 

tampering.

6.  The use of accessory equipment not recommended by Beluce Canada Inc. may cause an unsafe condition, and will 

void the unit’s warranty.

7.  Do not use this equipment for other than its intended purpose.
8.  Servicing of this equipment should be performed by qualified service personnel.

9.  SAVE THESE INSTRUCTIONS!

INSTRUCTIONS

INSTALLATION

      STRAP MOUNTING

1.  Extend unswitched 24 hour AC supply of rated voltage installed in accordance with all applicable codes and 

standards. Leave at least 8 inches of slack wire. This circuit should NOT be energized/live at this time.

2.  Knock out 

7

8

" power entry hole on top of unit.

3.  Mount the unit securely into place. Install four (4) screws. Fasten each strap with an appropriately sized screw or 

mounting bolt (not supplied) through each hole and into the mounting surface. Each fastener must be securely  
in place to properly support the unit (Figure 1).

4.  Open the unit by unscrewing the two (2) lens screws and (2) cover screws. Let cover assembly hang on tether  

(Figure 2) (Figure 3).

5.  Install conduit bushing (Figure 6).
6.  Make proper wiring connections between the AC supply and the unit’s transformer per diagram provided (Figure 4). 

Insulate unused wire seperately!

 Connect ground to supplied green ground wire in accordance with local codes. 

Reassemble all wire connections and connectors. 

CAUTION! - Failure to insulate unused wire may result in a 

shock hazard or unsafe condition as well as equipment failure. All wires must be dressed and routed to ensure 
they will not come in contact with the circuit board.

7.  Connect the wire lead(s) from the positive circuit board terminal (+) to the positive terminal connector on the battery 

(Figure 3). For large units the batteries may be shipped separate from the cabinet. Install the batteries into the cabinet 
and make the appropriate inter-battery connections (Figure 5).

8.  Secure batteries tightly with the provided velcro strap.
9.  Close cover and secure cover screws.
10.  Position lamps/heads to provide best lighting distribution. Manually rotate or twist head to desired position.
11.  Close lens and secure with (2) screws.
12.  Turn on AC line voltage supply.

      JUNCTION BOX MOUNTING

1.  See 1, 3 and 4 above.
2.  Knock out appropriate mounting hole in back of base (Figure 7).
3.  Install gasket between housing and junction box (Figure 7).
4.  Mount base to junction box.
5.  See 6 –12 above.

Bravado Unit (BRV)

OPERATION

      MAGNETIC TEST

1.   To test, pass a magnet over test marking to initiate the test (Figure 1). Charge indicator will go out and the DC lamps 

will come on.

      TEST BUTTON

1.   Open unit by unscrewing (2) lens screws and press test button.

 
 

A bright charge indicator indicates a high charge rate. After the battery has reached full charge, the indicator light will 
go out. Under normal operation the high charge indicator will turn off and on intermittently while the unit is in standby 
mode (regular/mains AC present) since the charge rate will vary in order to maintain an optimal battery charge.

926000307

Beluce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673

04/09/2019

Reviews: