Operation (Front Panel) – 3
3–11
3.3
Checkout Status/Metering
The relay has two menu selections concerning
monitoring status and demand values. This section
describes the operation of these selections.
Status/Metering
Access the
STATUS
menu as follows:
1.
Press
ENTER
to bring up the main
menu.
2.
Press the right arrow button until
STATUS
appears on the top line of the
display.
3.
Press
ENTER
to access the
STATUS
submenu and begin the monitoring.
■
■
■
■
■
NOTE:
Each category listed below is a
submenu item. Pressing the
ENTER
button moves the item down within that
menu, allowing monitoring of values
within that submenu category. To exit a
specific category and continue to the
next menu category, press the
EXIT
button.
All metering values in this section (with the
exception of power metering) are secondary level
quantities.
The menu categories for monitored values are:
VOLTAGE STATUS
Phase voltages, neutral voltage, V2 voltage,
positive sequence voltage, negative sequence
voltage, zero sequence voltage
CURRENT STATUS
Phase currents, neutral current, positive sequence
current, negative sequence current, zero sequence
current
FREQUENCY STATUS
Frequency, Rate of change of frequency
POWER STATUS
Real power, Reactive power, Apparent power,
Power factor
IMPEDANCE STATUS
SYNC CHECK STATUS
IN/OUT STATUS
Status of input and output contacts
The following timer status can also be monitored:
VOLTAGE TIMER
27, 27G, 47, 59, 59I, 59G
CURRENT TIMER
46, 50, 50G, 51G, 51V, 67
FREQUENCY TIMER
81, 81R
POWER TIMER
32
DISTANCE TIMER
21
SYNC CHECK TIMER
25
FUSE LOSS TIMER
60FL
RECONNECT TIMER
79
Timers for the inverse time functions are displayed
in percentage where 100% corresponds to the full
value of the integrating timer.
If the associated function time setting is less than
2 cycles, the indicated status will be less than
actual. The following miscellaneous status can
also be monitored:
COUNTERS
OUT1–8 plus alarm
TIME OF LAST POWER UP
ERROR CODES
Last error code log
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...