2–26
M-3520 Instruction Book
Sets phase current pickup for 51V.
Selects one of the eight inverse time curves as shown in
Appendix D, Figures D-1 through D-8.
The appropriate curve in the selected family of curves is
chosen here.
Restraint/control setting.
Voltage control level.
If this function is enabled, the following settings are applicable:
51V PICKUP
________ Amps
51V CURVE
DEF inv vinv einv
51V TIME DIAL
________
51V VOLTAGE CONTROL
disable V_CNTL v_rstrnt
51V VOLTAGE CONTROL
________ Volts
Input Voltage (% of Nominal Voltage)
0
25
50
75 100
0
25
50
75
100
Tap Setting as % of
Tap Setting at
Nominal Voltage
Figure 2-16
Voltage Restraint (51V) Characteristic
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...