M-3520 Instruction Book
6–24
50 Instantaneous Phase Overcurrent
VOLTAGE INPUTS:
None
CURRENT INPUTS:
Configuration C1
TEST SETTINGS:
Pickup
P
Amps
(1.0 to 240.0)
1 Amp CT Rating
(0.2 to 48.0)
Programmed Outputs
Z
Output
(1 to 8)
Function 51V
Disable
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedures.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration C1 designated previously. Refer to Section 6.4, Input Configurations,
for configurations.
4.
Pickup Test
: Hold the
TARGET RESET
button in and slowly increase the Phase A current until the
50 PHASE INST O/C
LED illuminates or the pickup indicator operates on the computer target
screen. The level of operation will be
P
Amps
&
0.1 A (
&
0.02 A for 1 Amp units) or
&
3%. Release
the
TARGET RESET
button and decrease the current and the
OUTPUT
LED’s will extinguish. Press
TARGET RESET
button to remove targets. This test may be repeated for each of the other phases.
5.
Time Test
: With output contact (
Z
) connected to the timer, apply current 5% above pickup (
P
) and
start timing. The operating time will be under 4 cycles.
6.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...