Testing – 6
6–13
21 Phase Distance (#1 or #2) Line to Line
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
Configuration C1
TEST SETTINGS:
Diameter
C
Ohms
(0.1 to 100)
1 Amp CT Rating
(0.5 to 500.0)
Offset
O
Ohms
(–100 to 100)
5 Amp CT Rating
(–500.0 to 500.0)
Impedance Angle
A
Degrees
(0 to 90)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
Output
(1 to 8)
Function 60FL, 21 (1 or 2)
Disable
Delta-Y Transform
Disable
■
■
■
■
■
NOTE:
It would be efficient to disable the function with the higher “reach” (Diameter plus Offset)
setting first (
lower current), and test the lower reach setting operation, since the higher reach setting
operation can be tested without disabling the lower setting.
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect input in Configuration V1 and C1 as designated above. Refer to Section 6.1, Equipment/Test
Setup for configurations.
4.
The level of current at which operation is to be expected for an individual setting is as follows:
a. Define “reach” as
R
ohms = (
C
ohms +
O
ohms) offset,
O
, usually set at zero ohms.
b. Define “current” as
I
= ((Selected Voltage / S3) I
R
ohms). The voltage level may be selected
based on the desired test current level.
5.
Pickup Test
: Set the three-phase voltages to the Selected Voltage value from step 4. Set the phase
angle between the voltage and current inputs at (
A
–30°) degrees from setting above. Hold the
TARGET RESET
button in and slowly increase the three-phase currents until the appropriate
PHASE DISTANCE 21
LED light goes on, or the pickup indicator operates on the computer target
screen. The level should be equal to
I
calculated in step 4 with the resulting impedance ±0.1 ohms or
5%. Release the
TARGET RESET
button and decrease the
INPUT CURRENTS
, and
OUTPUT
LEDs will go out. Press
TARGET RESET
button to remove targets.
6.
Time Test
: With output contacts connected to the timer, apply approximately 110% of the current (
I
)
found in step 4, and start timing. The contacts will close after
D
cycles within –1 to +3 cycles or 1%.
7.
If testing is complete, enable any functions disabled for this test. If other tests are to be completed,
check the proper functions to disable for the next test and proceed from this configuration.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...